| Date |
Text |
| 2019-11-27 11:51:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET 2 1.2 - THERE IS AN INDICATION THAT THE |
| | PROPOSED WILL HAVE FIRE SPRINKLERS. |
| | |
| | THERE ARE NO FIRE SPRINKLER DOCUMENTS ATTACHED. |
| | |
| | PER FLORIDA STATUTUE FIRE SPRINKLER DOCUMENTS ARE |
| | REQUIRED TO BE SUBMITTED WITH THIS MASTER PERMIT. SHOP |
| | DRAWINGS WILL BE BASED ON THE EOR AND SUBMITTED FROM |
| | THIS SUBMITTAL. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING |
| | DOCUMENTS. |
| | (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF |
| | PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR |
| | INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING |
| | PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S |
| | RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, |
| | 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: |
| | (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS |
| | REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A |
| | RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND |
| | EXPERIENCE. |
| | (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY |
| | STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH |
| | THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS |
| | ARE INTENDED TO CONFORM TO. |
| | (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF |
| | RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF |
| | THE SYSTEM. |
| | (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT |
| | SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING |
| | DOCUMENTS. |
| | (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY |
| | FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE |
| | ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE |
| | STATED PURPOSE OF THESE RESPONSIBILITY RULES. |
| | (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND |
| | BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING |
| | DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR |
| | CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE |
| | OF SUCH DOCUMENTS. |
| | (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN |
| | ENGINEERING DOCUMENT ONLY FOR INFORMATION OR |
| | CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO |
| | ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER |
| | SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS |
| | RESPONSIBILITY. |
| | (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY |
| | DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST |
| | ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS. |
| | (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY |
| | ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN |
| | FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC |
| | AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND |
| | INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE |
| | REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES |
| | WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE |
| | AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A |
| | PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR |
| | AGENCY APPROVAL ACTION ON THE SAME PROJECT. |
| | SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW |
| | IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW |
| | 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08. |
| | |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| | 4-2-2000, 6-26-01 |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | PLEASE REVIEW AND SUBMIT EITHER PLAN SHEETS OR A |
| | WRITTEN NARRATIVE, BOTH SIGNED AND SEALED BY THE EOR |
| | FOR REVIEW. |
| | |
| | |
| | 2) SHEET A 1.1 & A 8.1 - THERE ARE INDICATIONS ON THE |
| | DOOR SCHEDULE OF NO HARDWARE AND ONE OF THE # 1 WHICH |
| | SHOWS A LOCKSET. |
| | |
| | THE DOOR HARDWARE SHALL COMPLY WITH NFPA 101, CH 7, |
| | MEANS OF EGRESS, AND PER THE APPLICABLE OCCUPANCY |
| | CHAPTER. |
| | |
| | NFPA CH 12, NEW ASSEMBLY - |
| | |
| | 12.2.2.2 DOORS. |
| | 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 12.2.2.2.2 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF |
| | 300 OR LESS IN |
| | MALLS (SEE 36.4.4.4.2(4) SHALL BE PERMITTED TO HAVE |
| | HORIZONTAL OR VERTICAL |
| | SECURITY GRILLES OR DOORS COMPLYING WITH 7.2.1.4.1(3) |
| | ON THE MAIN |
| | ENTRANCE/EXITS. |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS |
| | PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS |
| | AS PERMITTED IN 12.2.2.2.6. |
| | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| | SHALL BE PERMITTED |
| | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| | IF BOTH OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY |
| | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY |
| | OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| | RELEASED |
| | BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | NFPA 101, CH 7 |
| | |
| | 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE. |
| | 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE |
| | EQUIPPED WITH |
| | PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET |
| | ALL OF THE |
| | FOLLOWING CRITERIA: |
| | (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE |
| | ACTUATING |
| | PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF |
| | OF THE |
| | WIDTH OF THE DOOR LEAF. |
| | (2) IT SHALL BE MOUNTED AS FOLLOWS: |
| | (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN. |
| | (865 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30 |
| | IN. (760 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE |
| | NOT TO EXCEED |
| | 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND |
| | LATCHES. |
| | 7.2.1.7.2* ONLY APPROVED FIRE EXIT HARDWARE SHALL BE |
| | USED ON FIRE |
| | PROTECTION-RATED DOOR ASSEMBLIES. NEW PANIC HARDWARE |
| | AND NEW |
| | FIRE EXIT HARDWARE SHALL COMPLY WITH ANSI/UL 305, |
| | STANDARD FOR |
| | SAFETY PANIC HARDWARE, AND ANSI/BHMA A156.3, EXIT |
| | DEVICES. |
| | 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT |
| | HARDWARE, IN OTHER |
| | THAN DETENTION AND CORRECTIONAL OCCUPANCIES AS |
| | OTHERWISE PROVIDED |
| | IN CHAPTERS 22 AND 23, SHALL NOT BE EQUIPPED WITH ANY |
| | LOCKING |
| | DEVICE, SET SCREW, OR OTHER ARRANGEMENT THAT PREVENTS |
| | THE RELEASE |
| | OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING |
| | DEVICE. |
| | 7.2.1.7.4 DEVICES THAT HOLD THE LATCH IN THE RETRACTED |
| | POSITION SHALL |
| | BE PROHIBITED ON FIRE EXIT HARDWARE, UNLESS SUCH |
| | DEVICES ARE LISTED |
| | AND APPROVED FOR SUCH A PURPOSE. |
| | |
| | FOR BUSINESS/MERCANTILE |
| | |
| | 38.2.2.2 DOORS. |
| | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED |
| | ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS |
| | |
| | 36.2.2.2 DOORS. |
| | 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED |
| | ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | NFPA 101, CH 7 |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | 7.2.1.5.5.2 THE ALTERNATIVE PROVISIONS OF 7.2.1.5.5.1 |
| | SHALL BE PERMITTED |
| | TO BE REVOKED BY THE AUTHORITY HAVING JURISDICTION FOR |
| | CAUSE. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS THAT ARE IN |
| | COMPLIANCE WITH THE ABOVE ON THE APPLICABLE DOORS |
| | |
| | |
| | |
| | 3) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF EXIT |
| | LIGHTS AND/OR EMERGENCY LIGHTING PER THE APPLICABLE |
| | OCCUPANCY CODE |
| | |
| | NFPA 101, CH 7 |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND |
| | STRUCTURE WHERE |
| | REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF |
| | THIS |
| | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE |
| | PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY |
| | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | CONTINUOUS DURING THE |
| | TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE |
| | MEANS OF EGRESS |
| | BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN |
| | 7.8.1.2.2. |
| | |
| | 7.9 EMERGENCY LIGHTING. |
| | 7.9.1 GENERAL. |
| | 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| | EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| | FOLLOWING: |
| | (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| | 11 THROUGH 43 |
| | |
| | CH 12, NEW ASSEMBLY |
| | |
| | 12.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF |
| | EGRESS, OTHER THAN |
| | FOR PRIVATE PARTY TENTS NOT EXCEEDING 1200 FT2 (112 M2) |
| | , SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | |
| | 12.2.9 EMERGENCY LIGHTING. |
| | 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| | ACCORDANCE WITH |
| | SECTION 7.9. |
| | |
| | CH 38 NEW BUSINESS |
| | |
| | 38.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | |
| | CH 36 NEW MERCANTILE |
| | |
| | 36.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | 36.2.9 EMERGENCY LIGHTING. CLASS A AND CLASS B |
| | MERCANTILE |
| | OCCUPANCIES AND MALL BUILDINGS SHALL HAVE EMERGENCY |
| | LIGHTING |
| | FACILITIES IN ACCORDANCE WITH SECTION 7.9. |
| | |
| | PLEASE REVIEW AND CORRECT AS APPLICABLE |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |