| Date |
Text |
| 2020-01-31 09:49:36 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL) |
| | |
| | A) OK. |
| | |
| | B) ORIGINAL COMMENT: |
| | ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| | RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED |
| | ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY |
| | CITY POLICY FOR ALL ROOFING PERMITS. |
| | |
| | RESPONSE: |
| | POLYSET RTA-1 ADHESIVE (NOA 18-0131.02) IS NOT LISTED |
| | ON THE ROOF TILE (NOA 19-1021.02) SUBMITTED. PROVIDE |
| | PRODUCT APPROVAL FOR ADHESIVE THAT IS LISTED ON THE |
| | APPROVED ROOF TILE. AND, REPAST COMMENT, CLEARLY MARK |
| | PADDY SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING. |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) NEW ROOF TILE ADHESIVE |
| | REQUIRED ON PREVIOUS ITEM . SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |