| Plan Review Notes For Permit 19101604 |
| Permit Number |
19101604 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-05 11:31:33 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE BACKFLOW PREVENTOR IS INDICATED CLOSE TO THE | | | BUILDING WITH NO DIMENSIONS PROVIDED. | | | | | | PER NFPA 24 | | | | | | 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS | | | FOR FIRE | | | PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH | | | ONE | | | OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED | | | | | | | | | (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING | | | VALVE NOT | | | LESS THAN 40 FT (12 M) FROM THE BUILDING | | | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A | | | BACKFLOW | | | PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL | | | BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) | | | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF | | | THE WALL FACING THE BACKFLOW PREVENTER. | | | | | | PLEASE INSTALL THE BACKFLOW AS FAR AWAY FROM THE | | | BUILDING AS POSSIBLE AS REQUIRED FOR THE MINIMUM | | | PROPERTY LINE DISTANCES. | | | | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|