| 2019-11-19 11:22:45 | PLAN REVIEW - ELECTRICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE AN ELECTRICAL SCOPE OF WORK AND IF NECESSARY |
| | AN ELECTRICAL RISER DIAGRAHM. CANNOT DETERMINE IF |
| | ADDITIONAL LOADS WILL BE ADDED. |
| | |
| | E3401.4 ADDITIONS AND ALTERATIONS. |
| | ANY ADDITION OR ALTERATION TO AN EXISTING ELECTRICAL |
| | SYSTEM SHALL BE MADE IN CONFORMITY TO THE PROVISIONS OF |
| | CHAPTERS 34 THROUGH 43. WHERE ADDITIONS SUBJECT |
| | PORTIONS OF EXISTING SYSTEMS TO LOADS EXCEEDING THOSE |
| | PERMITTED HEREIN, SUCH PORTIONS SHALL BE MADE TO COMPLY |
| | WITH CHAPTERS 34 THROUGH 43. |
| | E3403.2 INSPECTION REQUIRED. |
| | NEW ELECTRICAL WORK AND PARTS OF EXISTING SYSTEMS |
| | AFFECTED BY NEW WORK OR ALTERATIONS SHALL BE INSPECTED |
| | BY THE BUILDING OFFICIAL TO ENSURE COMPLIANCE WITH THE |
| | REQUIREMENTS OF CHAPTERS 34 THROUGH 43. |
| | E3403.3 LISTING AND LABELING. |
| | ELECTRICAL MATERIALS, COMPONENTS, DEVICES, FIXTURES AND |
| | EQUIPMENT SHALL BE LISTED FOR THE APPLICATION, SHALL |
| | BEAR THE LABEL OF AN APPROVED AGENCY AND SHALL BE |
| | INSTALLED, AND USED, OR BOTH, IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTALLATION INSTRUCTIONS. [110.3(B)] |
| | |
| | |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2 |
| | |
| | |