| Plan Review Notes For Permit 19101554 |
| Permit Number |
19101554 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-16 09:11:39 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) RISER SHOW A 200A BUSS DISCONNECT, PLEASE SUBMIT A | | | LOAD CALCULATION FOR THE LOAD ON THIS SWITCH. 215.5 | | | | | | 215.5 DIAGRAMS OF FEEDERS | | | IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, A | | | DIAGRAM SHOWING | | | FEEDER DETAILS SHALL BE PROVIDED PRIOR TO THE | | | INSTALLATION OF | | | THE FEEDERS. SUCH A DIAGRAM SHALL SHOW THE AREA IN | | | SQUARE FEET OF | | | THE BUILDING OR OTHER STRUCTURE SUPPLIED BY EACH | | | FEEDER, THE TOTAL | | | CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE | | | DEMAND | | | FACTORS USED, THE CALCULATED LOAD AFTER APPLYING DEMAND | | | FACTORS, | | | AND THE SIZE AND TYPE OF CONDUCTORS TO BE USED. |
|