| 2019-11-18 18:17:32 | SCREEN ENCLOSURE BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- DESIGN WIND PRESSURES USED FOR CALCULATIONS ON SHEET |
| | "B" DON'T MATCH DESIGN WIND PRESSURES SHOWN ON TABLE |
| | 2002.4 FBC-BUILDING. REVISE INFORMATION ON THE TOP |
| | RIGHT CORNER OF THE SHEET AS REQUIRED. SEE TABLE 2002.4 |
| | FBC-BUILDING. |
| | NOTE: ALSO, REVISE INFORMATION ON SHEET 1 OF 1 WHERE |
| | THE SITE SPECIFIC LAYOUT IS SHOWN. |
| | |
| | 2- SCREEN ENCLOSURES PRIMARY STRUCTURAL MEMBERS SHALL |
| | BE DESIGNED FOR A 300 POUND LOAD APPLIED VERTICALLY |
| | DOWNWARD ALONG ANY 1 FOOT OF ANY MEMBER, NON OCCURRING |
| | SIMULTANEOUSLY WITH WIND LOAD). REVISE CALCULATIONS |
| | INFORMATION SHOWN ON SHEET B. SEE SEC. 2002.4 |
| | FBC-BUILDING. |
| | |
| | 3- THIS SCREEN ENCLOSURE IS FOR A POOL ENCLOSURE. SHOW |
| | HOW COMPLYING WITH THE RESIDENTIAL SWIMMING BARRIER |
| | REQUIREMENTS. PROVIDE SPECIFICATIONS FOR THE GATE |
| | SHOWING COMPLIANCE WITH SEC. R4501.17 FBC-RESIDENTIAL. |
| | |
| | 4- THERE ARE TOO MANY GENERAL DETAILS IN THIS |
| | SUBMITTAL. CLEARLY MARK ALL THE DETAILS THAT APPLY TO |
| | THIS PROJECT. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |