| 2020-01-02 09:08:27 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | 1. WATER HEATER SHALL BE PROVIDED WITH ACCESS FOR | | | INSPECTION, SERVICE, REPAIR AND REPLACEMENT WITHOUT | | | REMOVAL OF PERMANENT CONSTRUCTION TO COMPLY WITH FBC PL | | | 502.5 PER FBC RES P2601.1 | | | 2. PROVIDE A THERMAL EXPANSION CONTROL DEVICE IN COLD | | | WATER SUPPLY TO THE WATER HEATER TO COMPLY WITH FBC RES | | | P2903.4 | | | 3. NEW VENTS TRHROUGH ROOF SHALL NOT PENETRATE OR | | | PHYSICALLY INTRUDE UPON EXISTING CONCRETE TIE BEAM OR | | | BEAM BLOCK. | | | 4. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | | INSPECTOR'S APPROVAL | | | |
|