| 2019-11-14 14:41:41 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. PER WPB FBC 107.2.1, SHOW THAT THE ECOSMART 8 KW |
| | ELECTRIC TANKLESS WATER HEATER INDICATED ON PLAN SHEET |
| | E-1 IS CAPABLE OF PROVIDING ADEQUATE HOT WATER AS |
| | REQUIRED BY FBC RES P2108.1. PROVIDE MANUFACTURER?S |
| | SPECIFICATION FOR SELECTED WATER HEATER AND INDICATE |
| | THE DEVICE ON PLAN SHEET P-1. |
| | 2. PLAN SHEET P-1 PROVIDES A SANITARY RISER DIAGRAM AND |
| | A SANITARY PLAN VIEW LAYOUT. PIPING ON THE TWO DIAGRAMS |
| | DO NOT MATCH. PER WPB FBC 107.2.1, PLEASE CLARIFY. SEE |
| | DETAILS BELOW. |
| | A. THE BUILDING DRAIN EXITS THE BUILDING ON DIFFERENT |
| | WALLS |
| | B. THE RISER DIAGRAM IS CODE COMPLIANT.; THE PLAN VIEW |
| | IS NOT. THE WASHER AND SINK SHALL CONNECT DOWNSTREAM OF |
| | THE TUB TO COMPLY WITH FBC RES P3108. 1 WET VENTING. |
| | THE WET VENT CONFIGURATIONS ON THE TWO DIAGRAMS ARE NOT |
| | IN AGREEMENT. |
| | 3. RE: SANITARY RISER DIAGRAM: PER FBC RES P2604.4, |
| | SINK AND WASHER UNDER SLAB PIPING SHALL NOT RUN |
| | PARALLEL WITH BUILDING EDGE IN FOOTER. |
| | 4. WASHER VENT THROUGH THE ROOF SHALL NOT PENETRATE OR |
| | PHYSICALLY INTRUDE ON THE EXISTING CONCRETE TIE BEAM OR |
| | BOND BEAM. |
| | 5. HORIZONTAL WASHER DRAIN FROM TRAP TO VENT SHALL |
| | CONNECT TO VERTICAL ABOVE THE FLOOR TO COMPLY WITH FBC |
| | RES P2601.1 AND FBC PL 802.3.3 MAXIMUM STANDPIPE |
| | LENGTH. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |