2019-11-14 08:43:051ST REVIEW FBC-2010 MECHANICAL
 REVISION #19101484
 THE BRISTOL
 PERMIT #15111020
 11/13/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS- 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M5.08: INDICATE IN THE SEQUENCE OF OPERATION
 WHERE THE SMOKE CURTAINS ARE LOCATED- ON WHICH FLOORS
 AND WHICH ELEVATORS. THE NOTES SEEM TO INDICATE ALL
 ELEVATORS ON FLOORS 5-25. IS THAT CORRECT?- SECTION
 107.2.1 WPB.
  
 2) PLEASE REVISE THE SMOKE ANALYSIS TO INDIICATE THE
 LOCATIONS OF THE SMOKE CURTAINS AND THE SEQUENCE OF
 OPERATION- SECTION 107.2.1 WPB.
  
 3) PROVIDE A SPEC SHEET FOR THE SMOKE CURTAIN WITH AN
 APPROVAL SIGNATURE BY THE ENGINEER OF RECORD- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  