| Plan Review Notes For Permit 19101484 |
| Permit Number |
19101484 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-14 08:43:05 | 1ST REVIEW FBC-2010 MECHANICAL | | | REVISION #19101484 | | | THE BRISTOL | | | PERMIT #15111020 | | | 11/13/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE- 2010 | | | FBC M- FLORIDA MECHANICAL CODE- 2010 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS- 2010 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M5.08: INDICATE IN THE SEQUENCE OF OPERATION | | | WHERE THE SMOKE CURTAINS ARE LOCATED- ON WHICH FLOORS | | | AND WHICH ELEVATORS. THE NOTES SEEM TO INDICATE ALL | | | ELEVATORS ON FLOORS 5-25. IS THAT CORRECT?- SECTION | | | 107.2.1 WPB. | | | | | | 2) PLEASE REVISE THE SMOKE ANALYSIS TO INDIICATE THE | | | LOCATIONS OF THE SMOKE CURTAINS AND THE SEQUENCE OF | | | OPERATION- SECTION 107.2.1 WPB. | | | | | | 3) PROVIDE A SPEC SHEET FOR THE SMOKE CURTAIN WITH AN | | | APPROVAL SIGNATURE BY THE ENGINEER OF RECORD- SECTION | | | 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|