| Plan Review Notes For Permit 19101484 |
| Permit Number |
19101484 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-15 16:43:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) IT IS UNCLEAR WHERE OR HOW MANY SMOKE CURTAINS HAVE | | | BEEN INSTALLED. IT IS MY RECOLLECTION THAT ONLY A FEW | | | LOWER FLOORS IN A FEW SEPECIFC AREAS AHD SMOKE CURTAINS | | | INSTALLED. | | | | | | PLEASE PROVIDE A NARRATIVE AND PLAN SHEET FOR REVIEW | | | AND CLARIFICATION PURPOSES. | | | | | | | | | 2) THE SMOKE CONTROL ANALYSIS IS PROVIDED HOWEVER, | | | THERE ARE NO INDICATIONS OF WHAT OR WHERE ANY REVISIONS | | | TO THIS DOCUMENT ARE RECORED. | | | | | | THE CHANGE NARRATIVE SHEET ONLY INDICATES MS0.08. | | | | | | ANY REVISION TO THE SMOKE CONTROL DOCUMENT NEEDS TO BE | | | CALLED OUT IN DETAIL. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFYIN DETAILED | | | NARRATIVE. | | | | | | | | | 3) SHEET MS 0.08 - THERE IS A REVISION CLOUD INDICATING | | | COMMENTS 1) & 2) ABOUT ALL SMOKE CURTAINS ELEVATOR | | | LOBBIES BEING ACTIVATED AND SMOKE DETECTORS IN ALL | | | ELEVATOR LOBBIES (5-25) ACTIVATING THE ENTIRE BANK | | | SMOKE CURTAINS. | | | | | | PLEASE CLARIFY HOW MANY SMOKE CURTAINS HAVE BEEN | | | INSTALLED AND WHERE EXACTLY AND REVIEW THIS SEQUENCE OF | | | OPERATION FOR ACCURACY. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|