Plan Review Notes
Plan Review Notes For Permit 19101480
Permit Number 19101480
Review Stop B
Sequence Number 1
Notes
Date Text
2019-10-29 06:38:18***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1 PLEASE INDICATE WHICH SYSTEM WILL BE USED
 WITHIN THE PRODUCT APPROVALS. THE SELECTED SYSTEM NEEDS
 TO INDICATE THE ANCHOR SPACING THAT MEETS THE PRESSURE
 REQUIREMENTS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved