2020-02-05 16:40:43BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19101472
 2ND REVIEW: JANUARY 31, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
  
 405.7.4 FBC[A]CHANGE IN DIRECTION.RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM. ADVISORY 405.7 LANDINGS. RAMPS THAT DO NOT
 HAVE LEVEL LANDINGS AT CHANGES IN DIRECTION CAN CREATE
 A COMPOUND SLOPE THAT WILL NOT MEET THE REQUIREMENTS OF
 THIS CODE.
 -PLEASE SHOW AND DIMENSION CHANGE IN DIRECTION THAT
 MEETS 405.7.4 FOR SIZE AND SLOPE.
  
 505.10.1 FBC[A]TOP AND BOTTOM EXTENSION AT RAMPS.RAMP
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND
 BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A WALL,
 GUARD, OR THE LANDING SURFACE, OR SHALL BE CONTINUOUS
 TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
 -PLEASE SHOW HANDRAIL EXTENSIONS AT BOTTOM OF RAMP.
  