| 2019-11-15 19:09:17 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 212.2 |
| | PLEASE SHOW THE CLEAR FLOOR SPACE. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 2. BY COMBINING THE TENET SPACE IT IS REQUIRED TO |
| | PROVIDE A WATER FOUNTAIN COMPLYING WITH FBC PL TABLE |
| | 402.1 AND FBC ACC 211.2, |
| | |
| | 3. SHT. ON THE BOTTOM OF THE SHEET IN THE CENTER OF |
| | THETYP. MOUNTING SPEC SHOWS A MIRROR WITH BOTTOM OF THE |
| | REFLECTIVE SURFACE AT 40 MIN THE CODE REQUIRES IT TO BE |
| | 40" MAX TO THE BOTTOM. PER FBC ACC 603.3 |
| | |
| | 4. THE 10 GAL WATER HEATER IS TO SMALL FOR MULTIPLE |
| | FIXTURE THE 10 GAL HEATERS ARE DESIGNED FOR A SINGLE |
| | FIXTURE PROVIDE A LARGER HEATER OR MANUFACTURE |
| | SPECIFICATIONS THAT SHOWS SIZING FOR MULTIPLE FIXTURE |
| | DESIGNED TO RUN SIMULTANEOUSLY. PER WPB AMEND TO FBC |
| | 107.2.1 AND FBC PL TABLE 604.4 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |