| 2020-01-28 14:22:03 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19101431 |
| | 1/28/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A MECHANICAL SUB-PERMIT APPLICATION HAS BEEN |
| | SUBMITTED FOR INSTALLATION OF A WALK-IN COOLER AND |
| | REFRIGERATION SYSTEM, HOWEVER A SEPARATE PRIMARY PERMIT |
| | IS REQUIRED FOR THAT PORTION OF THE PROJECT. CONCERNING |
| | THE MASTER PERMIT FOR THE PROJECT, A MECHANICAL |
| | SUB-PERMIT IS REQUIRED FOR THE NEW AC SYSTEM AND BATH |
| | EXHAUST FAN- SECTION 107.1 WPB. |
| | |
| | 2) THE $8700.00 JOB VALUE ON THE MASTER PERMIT MUST BE |
| | INCREASED TO REFLECT THE COSTS OF THE NEW HVAC SYSTEMS- |
| | SECTION 109.3 WPB. |
| | |
| | 3) SHOW THE O/A DUCT AND DAMPER LOCATIONS ON THE PLAN |
| | AND PROVIDE DETAILS- SECTION C403.2.4.3 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |