2020-01-28 14:22:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101431
 1/28/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A MECHANICAL SUB-PERMIT APPLICATION HAS BEEN
 SUBMITTED FOR INSTALLATION OF A WALK-IN COOLER AND
 REFRIGERATION SYSTEM, HOWEVER A SEPARATE PRIMARY PERMIT
 IS REQUIRED FOR THAT PORTION OF THE PROJECT. CONCERNING
 THE MASTER PERMIT FOR THE PROJECT, A MECHANICAL
 SUB-PERMIT IS REQUIRED FOR THE NEW AC SYSTEM AND BATH
 EXHAUST FAN- SECTION 107.1 WPB.
  
 2) THE $8700.00 JOB VALUE ON THE MASTER PERMIT MUST BE
 INCREASED TO REFLECT THE COSTS OF THE NEW HVAC SYSTEMS-
 SECTION 109.3 WPB.
  
 3) SHOW THE O/A DUCT AND DAMPER LOCATIONS ON THE PLAN
 AND PROVIDE DETAILS- SECTION C403.2.4.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  