2019-10-31 15:45:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.01 - THERE IS AN INCOREECT EDITION OF THE
 CURRENT FLORIDA FIRE PREVENTION CODE; 5TH.
  
 THE CURRENT EDTION IS THE 6TH.
  
 PLEASE REVIEW AND CORRECT AND ENSURE COMPLAINCE.
  
  
 2) SHEET A 1.01 - THERE IS ONLY ONE EXIT INDICATED FROM
 THIS PROPOSED MERCANTILE OCCUPANCY.
  
 PER NFPA 101, CH 36, NEW MERCANTILE OCCUPANCIES
  
 36.2.4 NUMBER OF MEANS OF EGRESS.
 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH
 36.2.4.5:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
 36.2.4.2 EXIT ACCESS, AS REQUIRED BY 36.2.4.1(3), SHALL
 BE PERMITTED
 TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS
 COMMON PATHS OF TRAVEL BY 36.2.5.3.
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 THE DISTANCE IS NOT PROVIDED, PLEASE PROVIDE THE TRAVLE
 DISTANCE FROM THE REMOTE AREA WITHIN COMPLIANCE OR
 CORRECT WITH A 2ND EXIT.
  
  
  
 3) SHEET A 1.01 OR OTHERS - THERE IS NO INDICATIONS OF
 A DOOR SCHEDULE INCLUDING ALL HARDWARE AND
 LOCKS/LATCHES.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL
 ENTRANCE THAT IS
 REQUIRED TO SERVE AS AN EXIT SHALL BE DESIGNED AND
 CONSTRUCTED SO
 THAT THE PATH OF EGRESS TRAVEL IS OBVIOUS AND DIRECT.
 WINDOWS THAT,
 BECAUSE OF THEIR PHYSICAL CONFIGURATION OR DESIGN AND
 THE MATERIALS
 USED IN THEIR CONSTRUCTION, HAVE THE POTENTIAL TO BE
 MISTAKEN FOR
 DOOR OPENINGS SHALL BE MADE INACCESSIBLE TO THE
 OCCUPANTS BY
 BARRIERS OR RAILINGS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE PROVIDE IN COMPLIANCE WITH THE APPLICABLE CODE.
  
  
  
 4) SHEET C 1.0 - THERE IS AN INDICATIONS OF A RAILING
 WITH NO HANDRAIL ON THE OPPISITE SIDE.
  
 PER NFPA 101, CH 7
  
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  