| 2019-10-31 15:45:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1.01 - THERE IS AN INCOREECT EDITION OF THE |
| | CURRENT FLORIDA FIRE PREVENTION CODE; 5TH. |
| | |
| | THE CURRENT EDTION IS THE 6TH. |
| | |
| | PLEASE REVIEW AND CORRECT AND ENSURE COMPLAINCE. |
| | |
| | |
| | 2) SHEET A 1.01 - THERE IS ONLY ONE EXIT INDICATED FROM |
| | THIS PROPOSED MERCANTILE OCCUPANCY. |
| | |
| | PER NFPA 101, CH 36, NEW MERCANTILE OCCUPANCIES |
| | |
| | 36.2.4 NUMBER OF MEANS OF EGRESS. |
| | 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, |
| | EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH |
| | 36.2.4.5: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY |
| | STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM |
| | EVERY PART OF EVERY STORY. |
| | 36.2.4.2 EXIT ACCESS, AS REQUIRED BY 36.2.4.1(3), SHALL |
| | BE PERMITTED |
| | TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES |
| | PERMITTED AS |
| | COMMON PATHS OF TRAVEL BY 36.2.5.3. |
| | 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN |
| | A CLASS C |
| | MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE |
| | TO THE EXIT |
| | OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT |
| | EXCEED 75 FT |
| | (23 M). |
| | |
| | THE DISTANCE IS NOT PROVIDED, PLEASE PROVIDE THE TRAVLE |
| | DISTANCE FROM THE REMOTE AREA WITHIN COMPLIANCE OR |
| | CORRECT WITH A 2ND EXIT. |
| | |
| | |
| | |
| | 3) SHEET A 1.01 OR OTHERS - THERE IS NO INDICATIONS OF |
| | A DOOR SCHEDULE INCLUDING ALL HARDWARE AND |
| | LOCKS/LATCHES. |
| | |
| | PER NFPA 101, CH 7, MEANS OF EGRESS |
| | |
| | 7.2 MEANS OF EGRESS COMPONENTS. |
| | 7.2.1 DOOR OPENINGS. |
| | 7.2.1.1 GENERAL. |
| | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| | CONFORM TO |
| | THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE |
| | SPECIAL |
| | REQUIREMENTS OF 7.2.1. |
| | 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL |
| | ENTRANCE THAT IS |
| | REQUIRED TO SERVE AS AN EXIT SHALL BE DESIGNED AND |
| | CONSTRUCTED SO |
| | THAT THE PATH OF EGRESS TRAVEL IS OBVIOUS AND DIRECT. |
| | WINDOWS THAT, |
| | BECAUSE OF THEIR PHYSICAL CONFIGURATION OR DESIGN AND |
| | THE MATERIALS |
| | USED IN THEIR CONSTRUCTION, HAVE THE POTENTIAL TO BE |
| | MISTAKEN FOR |
| | DOOR OPENINGS SHALL BE MADE INACCESSIBLE TO THE |
| | OCCUPANTS BY |
| | BARRIERS OR RAILINGS. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE PROVIDE IN COMPLIANCE WITH THE APPLICABLE CODE. |
| | |
| | |
| | |
| | 4) SHEET C 1.0 - THERE IS AN INDICATIONS OF A RAILING |
| | WITH NO HANDRAIL ON THE OPPISITE SIDE. |
| | |
| | PER NFPA 101, CH 7 |
| | |
| | 7.2.2.4.1 HANDRAILS. |
| | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON |
| | BOTH SIDES, |
| | UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR |
| | 7.2.2.4.1.6. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |