| Plan Review Notes For Permit 19101417 |
| Permit Number |
19101417 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-28 18:50:05 | REVISED 11/19/19 | | | | | | | | | BUILDING REVIEW APPROVED WITH PROVISO. | | | (NOTE: PROVIDE REVISION BEFORE WINDOW BUCK INSPECTION): | | | | | | 1- REVISE EGRESS WINDOW NOTE ON SHEET A-01. THE NOTE | | | REFERENCES A 1994 CODE SECTION. CURRENT CODE IS 2017. | | | REVISE NOTE TO SHOW COMPLIANCE WITH EITHER SEC. 702.5 | | | FBC-EXISTING BUILDING OR SEC. R310.2 FBC-RESIDENTIAL | | | (2017). | | | | | | SEC. 702.5 FBC-EXISTING BUILDING REQUIRES SAME TYPE OF | | | MANUFACTURER'S LARGEST SIZE WINDOW THAT WILL FIT | | | WITHING THE EXISTING ROUGH OPENING OR OTHER STYLE THAT | | | PROVIDES EQUAL OR GREATER WINDOW OPENING AREA THAN THE | | | EXISTING WINDOW. | | | | | | 2- BASED ON ENGINEER'S LETTER SUBMITTED, THERE IS ROOF | | | RAFTERS REPAIR WORK. IF THESE SCOPE OF WORK IS PART OF | | | THIS PERMIT, THEN PROVIDE REVISED PLANS SHOWING | | | COMPLETE DETAILS/SPECIFICATIONS AND AREA OF WORK. OR | | | PROVIDE COMPLETE INFORMATION ON SEPARATE PERMIT. | | | NOTE: SPECS DESCRIBED ON THE LETTER ARE FOR MASONRY | | | CONSTRUCTION. THIS IS A WOOD FRAMED HOUSE. PROVIDE | | | INFORMATION THAT MATCHES HOUSE CONSTRUCTION. |
|