| Plan Review Notes For Permit 19101349 |
| Permit Number |
19101349 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-10-30 13:52:02 | MET WITH CONTRACTOR TO GO OVER COMMENTS. NEED SIGNED | | | AND SEALED RAS 117 CALCULATIONS. | | | CONTRACTOR P/U ONE COPY OF NOA 18-0919.07 FOR RAS 117 | | | CALCULATIONS. | | | | | | RESIDENTIAL (R3) RE-ROOF REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- SELECTED ASSEMBLY FROM GAF NOA 18-0919.07 DOESN'T | | | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. NEED TO | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS ( 2 | | | COPIES) AS REQUIRED BY LIMITATION #7 ON LAST PAGE ON | | | NOA. NEED THE CALCULATIONS TO MEET THE DESIGN PRESSURES | | | REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | 2- SINGLES ROOF PITCH LESS THAN 4:12 REQUIRES TWO | | | LAYERS OF UNDERLAYMENT . SEC. R905.2.2 FBC-RESIDENTIAL. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|