Plan Review Notes
Plan Review Notes For Permit 19101349
Permit Number 19101349
Review Stop B
Sequence Number 2
Notes
Date Text
2019-10-30 13:52:02MET WITH CONTRACTOR TO GO OVER COMMENTS. NEED SIGNED
 AND SEALED RAS 117 CALCULATIONS.
 CONTRACTOR P/U ONE COPY OF NOA 18-0919.07 FOR RAS 117
 CALCULATIONS.
  
 RESIDENTIAL (R3) RE-ROOF REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SELECTED ASSEMBLY FROM GAF NOA 18-0919.07 DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. NEED TO
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS ( 2
 COPIES) AS REQUIRED BY LIMITATION #7 ON LAST PAGE ON
 NOA. NEED THE CALCULATIONS TO MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
  
 2- SINGLES ROOF PITCH LESS THAN 4:12 REQUIRES TWO
 LAYERS OF UNDERLAYMENT . SEC. R905.2.2 FBC-RESIDENTIAL.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  