| 2020-02-04 06:19:29 | 1) SHTS.A200.1 & A 500 SHOW THE DOOR IN FRONT OF THE |
| | WATER CLOSET IN THE HANDICAP ACCESSIBLE TOILET STALL IN |
| | THE WOMEN'S RESTROOM.DOORS SHALL BE LOCATED IN THE |
| | FRONT PARTITION OR IN THE SIDE WALL OR PARTITION |
| | FARTHEST FROM THE WATER CLOSET PER FBC-ACCESS. |
| | SEC.604.8.1.2. |
| | 2) SHT. A200.1 SHOWS THE DOOR IN FRONT OF THE WATER |
| | CLOSET IN THE HANDICAP ACCESSIBLE TOILET STALL IN THE |
| | MEN'S RESTROOM.DOORS SHALL BE LOCATED IN THE FRONT |
| | PARTITION OR IN THE SIDE WALL OR PARTITION FARTHEST |
| | FROM THE WATER CLOSET PER FBC-ACCESS. SEC.604.8.1.2. |
| | 3) SHT. A500 - THE CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET IN THE TOILET COMPARTMENTS IS SHOWN AS 48 X56 |
| | INCHES. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| | THE REAR WALL PER FBC-ACCESS. SEC. 604.3.1. 2ND |
| | REQUEST. |
| | 4) SHT. A500 - SHOW THE HEIGHT OF THE MIRROR FROM THE |
| | FINISH FLOOR TO THE BOTTOM OF THE REFLECTIVE SERVICE OF |
| | THE MIRROR. THE HEIGHT OF THE MIRROR SHALL COMPLY WITH |
| | FBC-ACCESS. SEC.603.3. |
| | 5) SHT. A500 - THE REAR WALL GRAB BAR SHALL BE 36 |
| | INCHES LONG MINIMUM AND SHALL BE LOCATED IN ACCORDANCE |
| | WITH FBC-ACCESS. SEC. 604.5.2. 2ND REQUEST. |
| | 6) SHT. A500 - THE SEAT HEIGHT OF THE HANDICAP |
| | ACCESSIBLE WATER CLOSETS SHALL COMPLY WITH FBC-ACCESS. |
| | SEC. 604.4. SHOW COMPLIANCE ON THE PLANS. |
| | 7) SHT. A500 - TOILET PAPER DISPENSERS IN THE |
| | ACCESSIBLE TOILET COMPARTMENTS SHALL COMPY WITH |
| | FBC-ACCESS. SEC.604.7. SHOW COMPLIANCE ON THE PLANS. |
| | 2ND REQUEST. |
| | 8) SHT. A500 - ONE OF THE URINALS IN THE MEN'S RESTROOM |
| | SHALL COMPLY WITH FBC-ACCESS. SEC.605.2.SHOW COMPLIANCE |
| | ON THE PLANS. 2ND REQUEST. |
| | 9) SUBMIT ELEVATION DETAILS FOR ALLL HANDICAP |
| | ACCESSIBLE PLUMBING FIXTURES AND COMPONENTS. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 10) THE LAYOUT OF THE PLUMBING FIXTURES IN THE MEN'S |
| | ACCESSIBLE TOILET COMPARTMENT ON SHT. A200.1 DOES NOT |
| | CORRELATE WITH THE LAYOUT ON SHT. A500. CLARIFY. |
| | 11) SHT. A500 - THE STANDARD WATER CLOSET IN THE |
| | WOMEN'S RESTROOM IS SHOWN AS 1' - 6" TO THE CENTERLINE |
| | OF THE WATER CLOSET FROM THE SIDE PARTITION. THIS WOULD |
| | LEAVE 1' - 1" FROM THE OTHER PARTITION TO THE |
| | CENTERLINE. A MINIMUM OF 15 " IS REQUIRED PER |
| | FBC-PLUMBING SEC.405.3.1. |
| | 12) ONE OF THE STANDARD WATER CLOSET COMPARTMENTS IN |
| | THE WOMEN'S RESTROOM IS SHOWN AS 4' - 5" IN DEPTH. THE |
| | DEPTH OF THE STANDARD TOILET COMPARTMENTS SHALL COMPLY |
| | WITH FBC-PLUMBING SEC.405.3.1. |
| | 13) SHOW THE DEPTH OF ALL THE STANDARD TOILET |
| | COMPARTMENTS ON THE PLANS. WPB AMEND. TO FBC SEC. |
| | 107.2.1, FBC-PLUMBING SEC. 405.3.1. |
| | 14) SHT. A200.1 SHOWS THE WIDTH OF ONE OF THE STANDARD |
| | TOILET COMPARTMENTS AS 2' -11 1/2 INCHES WIDE AND SHT. |
| | A500 SHOWS THE SAME COMPARTMENT WITH A WIDTH OF 2' - 7 |
| | 1/2 INCHES WIDE. CLARIFY. |
| | 15) SHT. P100 - GENERAL PLUMBING NOTE #10 B.2 - THE |
| | WALL THICKNESS OF THE PIPE INSULATION FOR THE HOT WATER |
| | SHALL COMPLY WITH TABLE C403.2.1 OF THE FBC- ENERGY. |
| | REVISE THE NOTE. |
| | 16) SHT.P.400 - A BACKFLOW PREVENTION DEVICE IS |
| | REQUIRED ON THE DISHWASHERS PER FBC-PLUMBING SECS. |
| | 608.2, 608.3. |
| | 17) SHT.P400 SHOWS AN AIR ADMITTANCE VALVE ON THE |
| | FUTURE SANITARY LINE .AIR ADMITTANCE VALVES SHALL VENT |
| | ONLY FIXTURES THAT ARE ON THE SAME FLOOR LEVEL AND |
| | CONNECT TO A HORIZONTAL BRANCH DRAIN. FBC-PLUMBING SEC. |
| | 918.3.1. |
| | 18) WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN |
| | FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK, THE |
| | HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT |
| | PER FBC-PLUMBING SEC.918.3.1. HOW MANY FLOORS ARE IN |
| | THIS BUILDING? |
| | 19) THE FUTURE SANITARY LINE CANNOT BE DESIGNED AS A |
| | WASTE STACK VENT PER FBC-PLUMBING SEC. 913. |
| | 20) SHT. P400 - THE SANITARY RISER IS MISSING A WATER |
| | CLOSET IN THE WOMEN'S RESTROOM. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 21) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE |
| | RESTROOMS PER FBC- PLUMBING SEC.416.5. |
| | 22) INDICATE ON THE PLANS IF THERE IS AN EXISTING |
| | SERVICE SINK. IF NOT , ONE WILL BE REQUIRED. FBC_ |
| | PLUMBING TABLE 403.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |