| 2019-11-15 15:39:39 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE DETAILS SHOWING COMPLIANCE WITH THE |
| | FOLLOWING. WPB AMEND TO FBC 107.2.1 |
| | |
| | A) FBC ACC 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL |
| | BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| | MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE. |
| | |
| | B)FBC ACC 604.5.2 REAR WALL. THE REAR WALL GRAB BAR |
| | SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE |
| | CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE |
| | SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. |
| | |
| | C) FBC ACC 604.4 SEATS. THE SEAT HEIGHT OF A WATER |
| | CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES |
| | MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF |
| | THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A |
| | LIFTED POSITION. |
| | |
| | D) THE CLEAR FLOOR SPACE FOR THE TOILET IS SHOWN AS |
| | 48X56 IT COMPLY WITH FBC ACC 604.3.1 SIZE. CLEARANCE |
| | AROUND A WATER CLOSET SHALL BE 60 INCHES MINIMUM |
| | MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL. |
| | |
| | E)FBC ACC 603.3 MIRRORS. MIRRORS LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED |
| | ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH |
| | THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | F) FBC ACC 604.7 DISPENSERS. TOILET PAPER DISPENSERS |
| | SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR. |
| | |
| | G)FBC ACC 213.3.3 URINALS. WHERE MORE THAN ONE URINAL |
| | IS PROVIDED, AT LEAST ONE SHALL COMPLY WITH 605. |
| | 605.2 HEIGHT AND DEPTH. URINALS SHALL BE THE STALL-TYPE |
| | OR THE WALL-HUNG TYPE WITH THE RIM 17 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. URINALS SHALL BE 13 |
| | 1/2 INCHES DEEP MINIMUM MEASURED FROM THE OUTER FACE OF |
| | THE URINAL RIM TO THE BACK OF THE FIXTURE. |
| | 605.3 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR FORWARD APPROACH |
| | SHALL BE PROVIDED. |
| | |
| | H)SHT A500 HAS A NOTE FOR THE STALL PARTITIONS STATING |
| | THE BOTTOM 6" OFF THE FLOOR THE BOTTOM OF THE PARTITION |
| | SHALL BE A MIN OF 9" OFF THE FLOOR PER FBC ACC |
| | 604.8.1.4 TOE CLEARANCE. THE FRONT PARTITION AND AT |
| | LEAST ONE SIDE PARTITION SHALL PROVIDE A TOE CLEARANCE |
| | OF 9 INCHES MINIMUM ABOVE THE FINISH FLOOR AND 6 INCHES |
| | DEEP MINIMUM BEYOND THE COMPARTMENT-SIDE FACE OF THE |
| | PARTITION, EXCLUSIVE OF PARTITION SUPPORT MEMBERS. |
| | COMPARTMENTS FOR CHILDREN?S USE SHALL PROVIDE A TOE |
| | CLEARANCE OF 12 INCHES MINIMUM ABOVE THE FINISH FLOOR. |
| | |
| | I) THE WATER FOUNTAIN SHALL COMPLY WITH FBC ACC 602.1 |
| | GENERAL.DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND |
| | 602. |
| | 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT |
| | OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS |
| | SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | |
| | |
| | J)THE DOOR IN THE ACCESSIBLE TOILET STALL IN THE MENS |
| | BATHROOM CAN NOT BE IN FRONT OF THE TOILET TO BE ABLE |
| | TO INSTALL THE DOOR IN THAT LOCATION THE TOILET SHALL |
| | BE RELOCATED TO THE OTHER END OF THE STALL IN ORDER TO |
| | COMPLY WITH FBC ACC 604.8.1.2 DOORS. TOILET COMPARTMENT |
| | DOORS, INCLUDING DOOR HARDWARE, SHALL COMPLY WITH 404 |
| | EXCEPT THAT IF THE APPROACH IS TO THE LATCH SIDE OF THE |
| | COMPARTMENT DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF |
| | THE COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES |
| | MINIMUM. DOORS SHALL BE LOCATED IN THE FRONT PARTITION |
| | OR IN THE SIDE WALL OR PARTITION FARTHEST FROM THE |
| | WATER CLOSET. WHERE LOCATED IN THE FRONT PARTITION, THE |
| | DOOR OPENING SHALL BE 4 INCHES MAXIMUM FROM THE SIDE |
| | WALL OR PARTITION FARTHEST FROM THE WATER CLOSET. WHERE |
| | LOCATED IN THE SIDE WALL OR PARTITION, THE DOOR OPENING |
| | SHALL BE 4 INCHES MAXIMUM FROM THE FRONT PARTITION. THE |
| | DOOR SHALL BE SELF-CLOSING.A DOOR PULL COMPLYING WITH |
| | 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR NEAR |
| | THE LATCH. TOILET COMPARTMENT DOORS SHALL NOT SWING |
| | INTO THE MINIMUM REQUIRED COMPARTMENT AREA. |
| | |
| | 2. A BACKFLOW DEVISE IS REQUIRED ON THE SUPPLY TO THE |
| | REFRIGERATOR ICE MAKER ON THE 18TH FLOOR BREAK ROOM. |
| | PER FBC PL 608.3 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |