| 2019-11-15 08:21:06 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 19101300 |
| | W. P. B. PERMIT: 19011155 |
| | ADD: 250 S. AUSTRALIAN AVE. SUITE: 18TH FLOOR. |
| | CONT: HEDRICK BROTHERS |
| | TEL/ CONTACT: DARA NUNEZ |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. / NOV. 15TH/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A.200 18TH FLOOR CONSTRUCTION PLAN NOW SHOWS |
| | WALL TYPE R A 1 HOUR FIRE RATED WALL SURROUNDING THE |
| | SERVER ROOM. SHEET A102 PARTITION TYPE SHOWS THIS WALL |
| | TYPE R AS THE 1 HOUR FIRE RATED WALL. THE VAV 18-19 |
| | WHEN PENETRATING THE 1 HOUR FIRE RATED WALLS SHOWS FIRE |
| | DAMPERS. WHEN VIEWING THE VAV 18-13 WHEN THIS DUCT |
| | PENETRATES THE BACK WALL OF THE SERVER ROOM, 1 HOUR |
| | FIRE RATED WALL OF THERE IS NO FIRE DAMPER AS REQUIRED |
| | BY THE 2017 FBC-B SECTIONS 717.5 WHERE REQUIRED AND |
| | 717.5.4 FIRE PARTITIONS. |
| | |
| | 2A) SHEET M-210 MAKES REFERENCE TO A NEW MECHANICAL |
| | EQUIPMENT STAND AND REFERS TO DETAILS ON SHEET M-410. |
| | PLEASE NOTE THAT IN THE ORIGINAL PERMIT DOCUMENTS THAT |
| | WERE REVIEWED AND APPROVED THERE WAS NO SUCH SHEET |
| | LABELED M-410. |
| | PLEASE PROVIDE A DETAIL FOR THIS NEW ROOF TOP |
| | CONDENSER. IF THIS EQUIPMENT STAND IS A PREFABRICATED |
| | STAND THEN WILL NEED TO MEET THE REQUIREMENTS FOR |
| | COMPONENTS AND CLADDING. |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(G) PRE-ENGINEERED A/C STANDS |
| | |
| | 2B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 2C) 1510.10 MECHANICAL UNITS / CLEARANCES BELOW RAISED |
| | A/C UNITS. ROOF MOUNTED MECHANICAL UNITS SHALL BE |
| | MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES (203 MM) |
| | ABOVE THE ROOF SURFACE, OR WHERE ROOFING MATERIALS |
| | EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT SUPPORTS |
| | PROVIDING A MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH |
| | TABLE 1510.10. |
| | |
| | 3) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |