Plan Review Notes
Plan Review Notes For Permit 19101288
Permit Number 19101288
Review Stop B
Sequence Number 2
Notes
Date Text
2019-11-18 11:17:40PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED. SUBMITTAL WAS CHANGED TO DIGITAL.
  
 2) COMPLIED. SUBMITTAL WAS CHANGED TO DIGITAL.
  
 3) UPON FURTHER REVIEW IT HAS BEEN DETERMINED THAT AS A
 RESULT OF THIS MEMBRANE STRUCTURE BEING ERECTED ON A
 BUILDING, IT IS NOT CONSIDERED A TEMPORARY STRUCTURE
 AND IS REQUIRED TO MEET THE REQUIREMENTS OF FBC
 SECTIONS 3102.1 THROUGH 3102.8. FBC 3102.1 3102.1
 GENERAL. THE PROVISIONS OF SECTIONS 3102.1 THROUGH
 3102.8 SHALL APPLY TO AIR-SUPPORTED, AIR-INFLATED,
 MEMBRANE-COVERED CABLE, MEMBRANE-COVERED FRAME AND
 TENSILE MEMBRANE STRUCTURES, COLLECTIVELY KNOWN AS
 MEMBRANE STRUCTURES, ERECTED FOR A PERIOD OF 180 DAYS
 OR LONGER. THOSE ERECTED FOR A SHORTER PERIOD OF TIME
 SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE.
 MEMBRANE STRUCTURES COVERING WATER STORAGE FACILITIES,
 WATER CLARIFIERS, WATER TREATMENT PLANTS, SEWAGE
 TREATMENT PLANTS, GREENHOUSES AND SIMILAR FACILITIES
 NOT USED FOR HUMAN OCCUPANCY ARE REQUIRED TO MEET ONLY
 THE REQUIREMENTS OF SECTIONS 3102.3.1 AND 3102.7.
 MEMBRANE STRUCTURES ERECTED ON A BUILDING, BALCONY,
 DECK OR OTHER STRUCTURE FOR ANY PERIOD OF TIME SHALL
 COMPLY WITH THIS SECTION.
  
 4) COMPLIED. THE ELECTRONICALLY SUBMITTED PLAN
 DOCUMENTS HAVE VALID DIGITAL SIGNATURES.
  
 5) PARTIAL COMPLIANCE. PLEASE REVISE THE LIFE SAFETY
 PLAN TO SHOW THE CALCULATION FACTORS USED TO DETERMINE
 THE OCCUPANT LOADS AND THE NUMBER OF OCCUPANTS IN THE
 TERRACE AREA AND THE TENT AREA SEPARATELY. IT APPEARS
 THAT THE TENT AREA WILL HAVE MORE THAN 49 OCCUPANTS AND
 WILL REQUIRE A MINIMUM OF TWO EXITS PER FBC 1006.2.1.
 SHOW THE MEANS OF EGRESS FROM THE TENT TO THE EXIT
 ACCESS. FBC 3103.4
  
 6) COMPLIED. SHOWN ON LIFE SAFETY PLANS.
  
 7) COMPLIED. SHOWN ON LIFE SAFETY PLANS.
  
 8) COMPLIED. AREA WILL BE OFF LIMITS WHEN TENT IS NOT
 IN PLACE. NO ELEVATOR ACCESS AND SIGNAGE INDICATING
 THAT AREA IS OFF LIMITS.
  
 9) SINCE THIS BUILDING IS TYPE IIB CONSTRUCTION, THE
 MEMBRANE STRUCTURE (TENT) IS ALSO REQUIRED TO BE TYPE
 IIB CONSTRUCTION. SUBMIT DOCUMENTATION THAT THE FRAME
 IS NONCOMBUSTIBLE AND THE MEMBRANE IS EITHER
 NONCOMBUSTIBLE OR FLAME RESISTANT FBC 3102.3 TYPE OF
 CONSTRUCTION. NONCOMBUSTIBLE MEMBRANE STRUCTURES SHALL
 BE CLASSIFIED AS TYPE IIB CONSTRUCTION. NONCOMBUSTIBLE
 FRAME OR CABLE-SUPPORTED STRUCTURES COVERED BY AN
 APPROVED MEMBRANE IN ACCORDANCE WITH SECTION 3102.3.1
 SHALL BE CLASSIFIED AS TYPE IIB CONSTRUCTION. HEAVY
 TIMBER FRAME-SUPPORTED STRUCTURES COVERED BY AN
 APPROVED MEMBRANE IN ACCORDANCE WITH SECTION 3102.3.1
 SHALL BE CLASSIFIED AS TYPE IV CONSTRUCTION. OTHER
 MEMBRANE STRUCTURES SHALL BE CLASSIFIED AS TYPE V
 CONSTRUCTION.
  
 10) NEW COMMENT. THE ENGINEERING FOR THE MEMBRANE
 STRUCTURE IS BASED ON A VULT WIND SPEED OF 60 MPH,
 EXPOSURE CATEGORY D, RISK CATEGORY II AND ELEVATION 42
 FEET. IT FURTHER STATES THAT COMPONENTS OF THE
 STRUCTURE MAY BE OVERSTRESSED AT 60 MPH. FBC 3102.7
 REQUIRES THE MEMBRANE STRUCTURE TO COMPLY WITH CHAPTER
 16. THE WINDLOADS FOR THIS BUILDING IS 170 MPH VULT,
 EXPOSURE CATEGORY D, RISK CATEGORY II. THE CURRENT
 DESIGN DOES NOT COMPLY. FBC 3102.7 ENGINEERING DESIGN.
 THE STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO
 SUSTAIN DEAD LOADS; LOADS DUE TO TENSION OR INFLATION;
 LIVE LOADS INCLUDING WIND, SNOW OR FLOOD AND SEISMIC
 LOADS AND IN ACCORDANCE WITH CHAPTER 16. 3102.7.1
 LATERAL RESTRAINT. FOR MEMBRANE-COVERED FRAME
 STRUCTURES, THE MEMBRANE SHALL NOT BE CONSIDERED TO
 PROVIDE LATERAL RESTRAINT IN THE CALCULATION OF THE
 CAPACITIES OF THE FRAME MEMBERS.
  
 11) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONAL COMMENTS MAY RESULT
 WHEN THE REQUESTED ADDITIONAL INFORMATION IS SUBMITTED.