Plan Review Notes
Plan Review Notes For Permit 19101288
Permit Number 19101288
Review Stop B
Sequence Number 1
Notes
Date Text
2019-10-25 16:30:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF PERMIT DOCUMENTS. FBC107.1
 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION
 DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS,
 GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED
 IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION. THE
 CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES &
 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE SPECIAL
 CONDITIONS EXIST, THE BUILDING OFFICIAL IS AUTHORIZED
 TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS TO BE
 PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 2) THE PLANS THAT WERE SUBMITTED ARE TOO SMALL. FBC
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 3) THE WORK DESCRIPTION ON THE PERMIT APPLICATION
 INDICATES THAT THE TEMPORARY TENT WILL BE ERECTED FOR
 180 DAYS. DID YOU INTEND TO SPECIFY "LESS" THAN 180
 DAYS. PLEASE CLARIFY. FBC 3103.1
  
 4) THE ENGINEERED DOCUMENTS ARE REQUIRED TO HAVE
 ORIGNINAL HANDWRITTEN SIGNATURES. 61G15-23.003
 PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (4.1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF
 THE LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (4.2) THE LICENSEE MUST THEN USE A WET SEAL, A
 DIGITALLY CREATED SEAL, OR AN EMBOSSING SEAL PLACED
 PARTIALLY OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH
 PAGE REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL
 SHALL NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 5) SHOW THE MEANS OF EGRESS FROM THE TENT TO THE EXIT
 ACCESS. FBC 3103.4
  
 6) THE TENT AND ITS SUPPORTS, BRACING, FOUNDATION
 PEDESTALS, ETC. CAN NOT BLOCK OR HINDER EMERGENCY
 EGRESS FROM THE REST OF THE TERRACE DECK AREAS. FBC
 1003.6
  
 7) SHOW THE LOCATIONS OF THE TENT FOUNDATION PEDESTALS
 ON THE PLANS. FBC 107.2.1
  
 8) SPECIFY HOW THE PEDESTALS BE PROTECTED SUCH THAT
 THEY WILL NOT PRESENT A TRIPPING HAZARD WHEN THE TENT
 IS NOT INSTALLED. FBC 107.2.1
  
 9) PROVIDE THE CONSTRUCTION TYPE OF THE BUILDING THAT
 THE TENT WILL BE INSTALLED ON. FBC TABLE 601
  
 10) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONAL COMMENTS MAY RESULT
 WHEN THE REQUESTED ADDITIONAL INFORMATION IS SUBMITTED.