Plan Review Notes
Plan Review Notes For Permit 19101275
Permit Number 19101275
Review Stop P
Sequence Number 1
Notes
Date Text
2019-10-28 07:31:5610/28/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE NOTE ON LANDSCAPE PLANS A SHOW A PVB BACKFLOW
 AND A REDUCED PRESSURE ZONE (RPZ) IS REQUIRED AT THE
 WATER METER AND SHALL HAVE A SEPARATE PERMIT,
 CERTIFICATION AND FINAL INSPECTION PER WEST PALM BEACH
 CROSS CONNECTION MANUAL PER THE WPB A TO FBC SEC.
 107.2.1.
  
 2. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  