| 2019-11-07 07:24:19 | REVIEWED REMOTELY BY TIM HUNT | | | APPROVED WITH THE FOLLOWING REDLINES/PROVISO: | | | | | | INSTANTANEOUS WATER HEATER CONNECTIONS FOR PUBLIC | | | LAVATORIES, P0.1, CROSSED OFF. | | | | | | BREAKROOM SINK SHALL NOT BE TEMPERED BELOW 110F, | | | FBC-PLB 607.1 | | | | | | TANKLESS SHALL BE SIZED TO PRODUCE HOT WATER @ THE | | | DESIGN GPM OF THE FAUCET MANUFACTURE. SLOWING THE WATER | | | FLOW DOWN WILL NOT BE ALLOWED. | | | | | | |
|