| 2019-10-29 07:45:02 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19101246 |
| | ADD: 1555 PALM BEACH LAKES BLVD. SUITE # 1400 |
| | CONT: VERDEX CONSTRUCTION, INC. |
| | TEL: 561-756-6409 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. OCT. 29TH/ 2019 |
| | ACTION: DENIED |
| | |
| | 1A) THE LIFE SAFETY PLAN 002_ALS1.1 AND SHEET |
| | 003_A1.1.1 THE NUMBERING SYSTEM FOR ALL ROOMS DOES NOT |
| | CORRELATE FROM PAGE TO PAGE. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED, DISCREPANCY IN THE PLANS. |
| | |
| | 1B) THE LIFE SAFETY PLAN 002_ALS1.1 SHOWS TRAVEL |
| | DISTANCES TO (2) EXITS. THE PLAN DOES SHOW THE OVERALL |
| | DIAGONAL DISTANCE OF THE OFFICE SPACE, ALSO THE |
| | REQUIRED 1/3RD DIAGONAL DISTANCE APART OF 31 FEET 1 |
| | INCH AND THE ACTUAL DIAGONAL DISTANCE THE 2 EXITS ARE |
| | APART 47 FEET 7 INCHES. |
| | |
| | THE ISSUE IS THE DESIGNER OF RECORD HAS SHOWN 2 MEANS |
| | OF EGRESS. THE SECOND MEANS OF EGRESS THAT GOES THROUGH |
| | ROOM 1400.9 IS A FILE STORAGE ROOM. PLEASE REVIEW |
| | SECTION 1016.2 EGRESS THROUGH INTERVENING ROOMS (5) |
| | EGRESS SHALL NOT PASS THROUGH STORAGE ROOMS, CLOSETS OR |
| | SPACES USED FOR SIMILAR PURPOSES. |
| | |
| | PLEASE MEASURE YOUR COMMON PATH OF TRAVEL FROM THE MOST |
| | REMOTE POINT OF THE FILE STORAGE ROOM 1400.12 FOR |
| | TRAVEL DISTANCE TO THE FRONT EGRESS DOORS OF THE OFFICE |
| | SPACE. I MEASURED THE DISTANCE TO APPROXIMATELY 85 |
| | FEET. |
| | REVIEW TABLE 1006.2.1 SPACES WITH ONE EXIT OR EXIT |
| | ACCESS DOORWAY. THE MAXIMUM COMMON PATH OF TRAVEL FOR A |
| | FIRE SPRINKLERED BUILDING WITH AN OCCUPANT LOAD OF LESS |
| | THAN 30 FOR A BUSINESS OCCUPANCY WILL ALLOW YOU 100 |
| | FEET OF COMMON PATH OF TRAVEL. PLEASE ADJUST PLANS |
| | ACCORDINGLY. IF QUESTIONS PLEASE GIVE ME A CALL. |
| | |
| | 1C) SHEET 003_A.1.1. AS LABELED ON THE FLOOR PLAN, |
| | ENTRY DOOR TO THE STORAGE ROOM 1400.9 (LIFE SAFETY |
| | SHEET ROOM 1400.1.2.). THERE IS NO DEMO PLAN PROVIDED |
| | IN THIS SET OF PLANS TO KNOW IF THIS DOOR IS EXITING |
| | AND OR IF NEW. PLEASE NOTE THIS ISSUE HAS COME UP |
| | BEFORE IN PLAN REVIEW WITH THIS DESIGNER. WHOSE DOOR IS |
| | THIS, UNDER MANAGEMENT OR THE TENANT? WHAT IS THE |
| | STANDARD FOR THIS BUILDING? THIS DOOR DOES NOT COMPLY |
| | WITH THE: |
| | |
| | 2017 FBC-ACCESSIBILITY CODE MANEUVERING CLEARANCES. |
| | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| | GATES SHALL COMPLY WITH 404.2.4 (A). MANEUVERING |
| | CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY |
| | AND THE REQUIRED LATCH SIDE FOR SIDE CLEARANCE. THIS |
| | DOOR AS SHOWN DOES NOT HAVE 18 INCHES ON THE LATCH |
| | SIDE. |
| | |
| | 1D) UNDER COMMENT 1C) IF THE DOOR TO THE STORAGE ROOM |
| | 1400.9 (FLOOR PLAN) 1004.1.2(LIFE SAFETY PLAN) IS UNDER |
| | THE CONTROL OF THE TENANT AND IS EXISTING THEN |
| | DISPROPORTIONATE COST CAN KICK IN, UP TO 20 % OF THE |
| | VALUE OF WORK PERFORMED UNDER THIS PERMIT CAN GO TO |
| | ACCESSIBLE UPGRADES OR $16,000.00 OF VALUE IN MAKING |
| | THIS TENANT SPACE 100% ACCESSIBLE. |
| | |
| | 2017 ACCESSIBILITY CODE SECTION 202.4.1 |
| | DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE |
| | DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN |
| | THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO |
| | THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 2) THE SECOND ISSUE CAN BE FOUND ON SHEET 008_A3.1.1. |
| | THE HEIGHT OF THE RECEPTION DESK THE OVERALL HEIGHT OF |
| | THE RECEPTION DESK IS GIVEN AT 3 FEET 6 INCHES TALL. |
| | PLEASE REVIEW SECTION 904.3.3 OF THE 2017 ACCESSIBILITY |
| | CODE. WHERE PROVIDED, CHECK WRITING SURFACES SHALL |
| | COMPLY WITH 902.3. 404.2.4 902.3 HEIGHT. THE TOPS OF |
| | AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |