| 2019-11-14 13:35:52 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1) THIS IS AN ADDITION AND LEVEL 2 ALTERATION (SEC. |
| | 504.1 FBC-EXISTING BUILDING). PLANS SHOW REMOVING |
| | WINDOW FROM BEDROOM #2 TO ALLOW FOR THE GARAGE |
| | ENCLOSURE. ACCORDING TO CITY RECORDS PERMIT #14011326, |
| | THIS WINDOW WAS THE BEDROOM EGRESS WINDOW. SPECIFY THE |
| | TYPE AND SIZE OF THE OTHER WINDOWS TO REMAIN IN THIS |
| | BEDROOM TO VERIFY COMPLIANCE WITH EGRESS. SEC. R310.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 2) ROOF FRAMING PLAN SHOWS AN ATTIC ACCESS WITH PULL |
| | DOWN LADDER. IT LOOKS LIKE THE ATTIC IS GOING TO BE |
| | USED FOR STORAGE. REVISE THE ROOF LIVE LOADS SPECIFIED |
| | ON THE PROJECT DATA ON SHEET 2.1. NOTE: INCLUDE THE |
| | ATTIC LIVE LOAD AS REQUIRED BY SEC. R301.5 |
| | FBC-RESIDENTIAL AND CLEARLY SPECIFY THE TOP CHORD LIVE |
| | AND DEAD LOADS AND THE BOTTOM CHORD LIVE AND DEAD |
| | LOADS. |
| | |
| | 3- NEW CORNER COLUMNS SHOWN ON SHEET 2.1 ARE NOT CLEAR. |
| | ARE THEY C-2 TYPE COLUMNS?. SEC. 107.2.1 CITY |
| | AMENDMENTS. CLEARLY IDENTIFY COLUMN TYPE. |
| | |
| | 4- TYPICAL GABLE END WALL SECTION ON SHEET 5.1: PROVIDE |
| | COMPLETE SPECIFICATIONS FOR THE FASTENERS AT THE TOP |
| | AND BOTTOM OF 2X6 GABLE END WALL. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE |
| | EXISTING BEDROOMS AS REQUIRED BY SEC. R315.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 6- ARCHITECT OF RECORD TO SPECIFY ROOF TILE FASTENING |
| | AS REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. IF |
| | SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| | SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY |
| | PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL) |
| | |
| | A) ROOF TILE. |
| | |
| | B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| | RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED |
| | ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY |
| | CITY POLICY FOR ALL ROOFING PERMITS. |
| | |
| | C) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | D) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | |
| | E)PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | (INCLUDING ALL PRODUCT APPROVALS ALREADY SUBMITTED) AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |