2019-11-20 14:23:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101209
 11/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: PLEASE REFER TO TABLE 403.3.1.1: THE O/A
 VENTILATION RATE FOR DINING ROOMS IS CALCULATED AT 70
 PERSONS PER 1000 SF AT 7.5 CFMS PER PERSON + 0.18 CFMS
 PER SF. PLEASE CORRECT THE CALCULATION.
  
 2) THE REVISED AC CALULATIONS ARE INCORRECTLY LISTING
 THE PROJECT LOCATION AS ST. LUCIE WEST- PLEASE CORRECT.
  
 3) THE REVISED AC CALCULATIONS SHOW LIGHTING WATTAGE AT
 1413 (SEE ROOM INPUT ON PAGE 4), HOWEVER THE REVISED
 COMCHECK INTERIOR LIGHTING COMPLIANCE INDICATES 977
 WATTS. PLEASE NOTE THAT THE LIGHTING POWER DENSITIES
 ARE INDICATED AT 1253 WATTS ON E-1.
  
 4) THE ARCHITECT OF RECORD SHALL PROVIDE AN APPROVAL
 STAMP ON THE CORRECTED COMCHECK COMPLIANCE REPORT-
 SECTION 107.2.1 WPB. PLEASE INFORM ALTMAN BROTHERS LLC.
 THAT THEIR CONTRACTOR REGISTRATION WITH THE CITY OF WPB
 HAS EXPIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  