| 2019-11-20 14:23:09 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19101209 |
| | 11/20/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) M-1: PLEASE REFER TO TABLE 403.3.1.1: THE O/A |
| | VENTILATION RATE FOR DINING ROOMS IS CALCULATED AT 70 |
| | PERSONS PER 1000 SF AT 7.5 CFMS PER PERSON + 0.18 CFMS |
| | PER SF. PLEASE CORRECT THE CALCULATION. |
| | |
| | 2) THE REVISED AC CALULATIONS ARE INCORRECTLY LISTING |
| | THE PROJECT LOCATION AS ST. LUCIE WEST- PLEASE CORRECT. |
| | |
| | 3) THE REVISED AC CALCULATIONS SHOW LIGHTING WATTAGE AT |
| | 1413 (SEE ROOM INPUT ON PAGE 4), HOWEVER THE REVISED |
| | COMCHECK INTERIOR LIGHTING COMPLIANCE INDICATES 977 |
| | WATTS. PLEASE NOTE THAT THE LIGHTING POWER DENSITIES |
| | ARE INDICATED AT 1253 WATTS ON E-1. |
| | |
| | 4) THE ARCHITECT OF RECORD SHALL PROVIDE AN APPROVAL |
| | STAMP ON THE CORRECTED COMCHECK COMPLIANCE REPORT- |
| | SECTION 107.2.1 WPB. PLEASE INFORM ALTMAN BROTHERS LLC. |
| | THAT THEIR CONTRACTOR REGISTRATION WITH THE CITY OF WPB |
| | HAS EXPIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |