Plan Review Notes
Plan Review Notes For Permit 19101209
Permit Number 19101209
Review Stop P
Sequence Number 1
Notes
Date Text
2019-11-07 13:22:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 NOTE: A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS
 AS REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PER WPB FBC 107.2.1, ARCHITECT SHALL PROVIDE FOR
 RESTROOMS, RESTROOM LAYOUT WITH DIMENSIONS AND DOOR
 LOCATION ARE REQUIRED TO DETERMINE COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE SECTIONS.
 2. RE: A-1; ADA RESTROOM ELEVATIONS. PER FBC ACC 604.2,
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM FROM THE
 SIDE WALL OR PARTITION. PER WPB FBC 107.2.1, SHOW THE
 SAME.
 3. RE: A-1; ADA RESTROOM ELEVATIONS. PER FBC ACC 604.7,
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. PER WPB FBC 107.2.1,
 SHOW THE SAME.
 4. RE: PLAN SHEET P-1: PLUMBING NOTE 5: PER WPB FBC
 107.2.1 AND 107.3.5.1.3, CLEARLY SPECIFY THE TYPE
 POLYETHYLENE PIPING AND FITTINGS USED FOR WATER
 DISTRIBUTION CITING FBC PL TABLES 605.4 AND 605.5; LIST
 THE APPLICABLE STANDARD(S) OR CHANGE NOTE TO REQUIRE
 WATER DISTRIBUTION MATERIALS TO COMPLY WITH FBC PL
 TABLES 605.4 AND 605.5.
 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE GREASE
 INTERCEPTOR SPECIFICATION/CUT SHEETS. ELIMINATE DRY
 HORIZONTAL VENTS FROM 3 COMPARTMENT SINK DETAIL. THE GC
 HAS STATED THAT THE INTERCEPTOR WILL BE SET ON TOP OF
 THE SLAB, NOT IN IT. IF THIS IS THE CASE, PLEASE REVISE
 THE 3 COMPARTMENT SINK DETAIL TO REFLECT.
 6. PLEASE REFER TO UNDERGROUND PLUMBING REVIEW PERMIT
 #19090446, ISSUED 10/29/19. PLAN SHEET P-1;
 A) PLUMBING PROVISO FOR FUTURE VENT. PROVISO STATES
 HORIZONTAL DRY VENT NOT PERMITTED PER FBC PL
 903.3-903.4. P-1 THIS PERMIT IS STILL SHOWING THE
 PROHIBITED HORIZONTAL DRY VENT. REMOVE TO COMPLY.
 B) FLOOR SINKS FOR EQUIPMENT 8 AND 26 HAVE ADDED
 UNDERGROUND PIPING ON P-1 THIS PERMIT, WHICH APPEARS TO
 BE HORIZONTAL DRY VENTS. COMPLY WITH FBC PL
 903.3-903.4.
 C) IT IS NOTED THAT THE USE OF A POINT OF USE GREASE
 INTERCEPTOR AT THE FUTURE THREE COMPARTMENT SINK WAS
 APPROVED AND A WHOLE HOUSE INTERCEPTOR IS NOT REQUIRED.
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PLAN
 VIEW LAYOUT FOR COLD AND HOT WATER DISTRIBUTION; PLEASE
 NOTE THAT PER FBC PL 607.2, DEVELOPED LENGTH OF HOT
 WATER PIPING THAT EXCEEDS 50 FEET SHALL REQUIRE A
 RECIRCULATING SYSTEM OR HEAT TRACE SYSTEM WHICH
 COMPLIES WITH FBC PL 607.2.1 THROUGH 607.2.2.2.
 8. PER WPB FBC 107.2.1 AND 107.3.5.1.3, SHOW
 CALCULATIONS FOR AND CLEARLY SIZE THE COLD AND HOT
 WATER DISTRIBUTION.
 9. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CLEARLY
 INDICATE THE DELIVERY TEMPERATURE OF THE HOT WATER
 DISTRIBUTION.
 10. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE AND
 SPECIFY AND LOCATE BACKFLOW PREVENTERS TO COMPLY WITH
 FBC PL 608.1, FOR THE WATER SERVICE, ICE MAKER(S),
 COFFEE MAKER(S) AND EXPRESSO MACHINES(S).
 11. PER WPB FBC 107.2.1, PROVIDE WATER HEATER SCHEDULE
 NOTING MANUFACTURER, MODEL NUMBER, ELECTRICAL
 CHARACTERISTICS, NOTE WHETHER OR NOT, IT COMES WITH
 INTEGRAL HEAT TRAPS AND ENERGY PERFORMANCE EFFICIENCY
 AS REQUIRED BY FBC EC C404.2.
 12. PLAN SHEETS A-1, E-1 AND P-1 SHOWS A 50 GALLON
 WATER HEATER. P-2 SHOWS A 30 GALLON WATER HEATER.
 PLEASE CLARIFY. PER WPB FBC 107.2.1 AND 107.3.5.1.3,
 PROVIDE DETAIL FOR WATER HEATER MOUNTED ON SHELF ABOVE
 THE MOP SINK; IN ACCORDANCE WITH THE REQUIREMENTS OF
 FBC PL SECTIONS 503, 504 AND FBC PL 607.3, SHOW
 REQUIRED SHUT OFF AND RELIEF VALVES, EXPANSION TANK
 SHALL BE SIZED, HEAT TRAPS IF NOT INTEGRAL TO THE WATER
 HEATER, SIZED T & P DISCHARGE TO HUB DRAIN WITH
 REQUIRED AIR GAP (OR TO PAN WITH REQUIRED AIR GAP), PAN
 (SPECIFY MATERIAL TO COMPLY WITH FBC PL 504.7), SIZED
 PAN DRAIN TO IT?S POINT OF TERMINATION. RELIEF PIPING
 AND PAN DRAIN PIPING TO BE OF MATERIALS ALLOWED BY FBC
 PL TABLES 605.4 AND 605.5.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19101209 2602 S DIXIE HWY