| 2019-11-07 13:22:47 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | NOTE: A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS |
| | AS REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. PER WPB FBC 107.2.1, ARCHITECT SHALL PROVIDE FOR |
| | RESTROOMS, RESTROOM LAYOUT WITH DIMENSIONS AND DOOR |
| | LOCATION ARE REQUIRED TO DETERMINE COMPLIANCE WITH THE |
| | 2017 FBC-ACCESSIBILITY CODE SECTIONS. |
| | 2. RE: A-1; ADA RESTROOM ELEVATIONS. PER FBC ACC 604.2, |
| | THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM FROM THE |
| | SIDE WALL OR PARTITION. PER WPB FBC 107.2.1, SHOW THE |
| | SAME. |
| | 3. RE: A-1; ADA RESTROOM ELEVATIONS. PER FBC ACC 604.7, |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. PER WPB FBC 107.2.1, |
| | SHOW THE SAME. |
| | 4. RE: PLAN SHEET P-1: PLUMBING NOTE 5: PER WPB FBC |
| | 107.2.1 AND 107.3.5.1.3, CLEARLY SPECIFY THE TYPE |
| | POLYETHYLENE PIPING AND FITTINGS USED FOR WATER |
| | DISTRIBUTION CITING FBC PL TABLES 605.4 AND 605.5; LIST |
| | THE APPLICABLE STANDARD(S) OR CHANGE NOTE TO REQUIRE |
| | WATER DISTRIBUTION MATERIALS TO COMPLY WITH FBC PL |
| | TABLES 605.4 AND 605.5. |
| | 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE GREASE |
| | INTERCEPTOR SPECIFICATION/CUT SHEETS. ELIMINATE DRY |
| | HORIZONTAL VENTS FROM 3 COMPARTMENT SINK DETAIL. THE GC |
| | HAS STATED THAT THE INTERCEPTOR WILL BE SET ON TOP OF |
| | THE SLAB, NOT IN IT. IF THIS IS THE CASE, PLEASE REVISE |
| | THE 3 COMPARTMENT SINK DETAIL TO REFLECT. |
| | 6. PLEASE REFER TO UNDERGROUND PLUMBING REVIEW PERMIT |
| | #19090446, ISSUED 10/29/19. PLAN SHEET P-1; |
| | A) PLUMBING PROVISO FOR FUTURE VENT. PROVISO STATES |
| | HORIZONTAL DRY VENT NOT PERMITTED PER FBC PL |
| | 903.3-903.4. P-1 THIS PERMIT IS STILL SHOWING THE |
| | PROHIBITED HORIZONTAL DRY VENT. REMOVE TO COMPLY. |
| | B) FLOOR SINKS FOR EQUIPMENT 8 AND 26 HAVE ADDED |
| | UNDERGROUND PIPING ON P-1 THIS PERMIT, WHICH APPEARS TO |
| | BE HORIZONTAL DRY VENTS. COMPLY WITH FBC PL |
| | 903.3-903.4. |
| | C) IT IS NOTED THAT THE USE OF A POINT OF USE GREASE |
| | INTERCEPTOR AT THE FUTURE THREE COMPARTMENT SINK WAS |
| | APPROVED AND A WHOLE HOUSE INTERCEPTOR IS NOT REQUIRED. |
| | 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PLAN |
| | VIEW LAYOUT FOR COLD AND HOT WATER DISTRIBUTION; PLEASE |
| | NOTE THAT PER FBC PL 607.2, DEVELOPED LENGTH OF HOT |
| | WATER PIPING THAT EXCEEDS 50 FEET SHALL REQUIRE A |
| | RECIRCULATING SYSTEM OR HEAT TRACE SYSTEM WHICH |
| | COMPLIES WITH FBC PL 607.2.1 THROUGH 607.2.2.2. |
| | 8. PER WPB FBC 107.2.1 AND 107.3.5.1.3, SHOW |
| | CALCULATIONS FOR AND CLEARLY SIZE THE COLD AND HOT |
| | WATER DISTRIBUTION. |
| | 9. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CLEARLY |
| | INDICATE THE DELIVERY TEMPERATURE OF THE HOT WATER |
| | DISTRIBUTION. |
| | 10. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE AND |
| | SPECIFY AND LOCATE BACKFLOW PREVENTERS TO COMPLY WITH |
| | FBC PL 608.1, FOR THE WATER SERVICE, ICE MAKER(S), |
| | COFFEE MAKER(S) AND EXPRESSO MACHINES(S). |
| | 11. PER WPB FBC 107.2.1, PROVIDE WATER HEATER SCHEDULE |
| | NOTING MANUFACTURER, MODEL NUMBER, ELECTRICAL |
| | CHARACTERISTICS, NOTE WHETHER OR NOT, IT COMES WITH |
| | INTEGRAL HEAT TRAPS AND ENERGY PERFORMANCE EFFICIENCY |
| | AS REQUIRED BY FBC EC C404.2. |
| | 12. PLAN SHEETS A-1, E-1 AND P-1 SHOWS A 50 GALLON |
| | WATER HEATER. P-2 SHOWS A 30 GALLON WATER HEATER. |
| | PLEASE CLARIFY. PER WPB FBC 107.2.1 AND 107.3.5.1.3, |
| | PROVIDE DETAIL FOR WATER HEATER MOUNTED ON SHELF ABOVE |
| | THE MOP SINK; IN ACCORDANCE WITH THE REQUIREMENTS OF |
| | FBC PL SECTIONS 503, 504 AND FBC PL 607.3, SHOW |
| | REQUIRED SHUT OFF AND RELIEF VALVES, EXPANSION TANK |
| | SHALL BE SIZED, HEAT TRAPS IF NOT INTEGRAL TO THE WATER |
| | HEATER, SIZED T & P DISCHARGE TO HUB DRAIN WITH |
| | REQUIRED AIR GAP (OR TO PAN WITH REQUIRED AIR GAP), PAN |
| | (SPECIFY MATERIAL TO COMPLY WITH FBC PL 504.7), SIZED |
| | PAN DRAIN TO IT?S POINT OF TERMINATION. RELIEF PIPING |
| | AND PAN DRAIN PIPING TO BE OF MATERIALS ALLOWED BY FBC |
| | PL TABLES 605.4 AND 605.5. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| | DESIGNER PER WPB FBC 107.2.1. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19101209 2602 S DIXIE HWY |