Plan Review Notes
Plan Review Notes For Permit 19101209
Permit Number 19101209
Review Stop M
Sequence Number 1
Notes
Date Text
2019-10-25 14:48:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101209
 10/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: AN EXHAUST VENTILATION SYSTEM SIZED AT A RATE
 OF .7 CFMS PER SQ. FT. IS REQUIRED FOR THE KITCHEN, AND
 RECIRCULATION OF AIR FROM THE KITCHEN INTO THE DINING
 ROOM IS PROHIBITED- TABLE 403.3.1.1 FBC M.
  
 2) THE AC CALCULATIONS DO NOT SHOW ANY BTUH LOADS FOR
 PEOPLE- SECTION C403.2.1 FBC EC.
  
 3) SHOW THE LOCATION OF THE NEW RTU ON THE ROOF AND
 REQUIRED CLEARANCE DISTANCES TO EXHAUST OUTLETS, VENTS
 ETC- SECTION 401.4 FBC M.
  
 4) PROVIDE STRUCTURAL ENGINEERING FOR THE ROOF OPENING,
 INSTALLATION OF THE CURB, AND MOUNTING OF THE RTU-
 SECTION 301.15 FBC M.
  
 5) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 THE WALK IN COOLER- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  