| 2019-10-25 14:48:47 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19101209 |
| | 10/25/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) M-1: AN EXHAUST VENTILATION SYSTEM SIZED AT A RATE |
| | OF .7 CFMS PER SQ. FT. IS REQUIRED FOR THE KITCHEN, AND |
| | RECIRCULATION OF AIR FROM THE KITCHEN INTO THE DINING |
| | ROOM IS PROHIBITED- TABLE 403.3.1.1 FBC M. |
| | |
| | 2) THE AC CALCULATIONS DO NOT SHOW ANY BTUH LOADS FOR |
| | PEOPLE- SECTION C403.2.1 FBC EC. |
| | |
| | 3) SHOW THE LOCATION OF THE NEW RTU ON THE ROOF AND |
| | REQUIRED CLEARANCE DISTANCES TO EXHAUST OUTLETS, VENTS |
| | ETC- SECTION 401.4 FBC M. |
| | |
| | 4) PROVIDE STRUCTURAL ENGINEERING FOR THE ROOF OPENING, |
| | INSTALLATION OF THE CURB, AND MOUNTING OF THE RTU- |
| | SECTION 301.15 FBC M. |
| | |
| | 5) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR |
| | THE WALK IN COOLER- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |