| Plan Review Notes For Permit 19101207 |
| Permit Number |
19101207 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-05 16:44:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO INDICATIONS OF ACCESS GATES. FD | | | REQUIRES SITE ACCESS FOR EMERGENCY OR OTHER APPLICABLE | | | INCIDENTS. | | | | | | PER NFPA 1 | | | | | | 18.2.3.4 SPECIFICATIONS. | | | 18.2.3.4.1 DIMENSIONS. | | | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | | UNOBSTRUCTED | | | WIDTH OF NOT LESS THAN 20 FT | | | | | | | | | PLEASE PROVIDE A MINIMUM OF 2 - 10' GATES THAT IS | | | EASILY ACCESSIBLE FROM A ROADWAY. | | | | | | | | | | | | 2) KNOX PADLOCKS ARE RECOMMENDED FOR EACH GATE FOR EASE | | | OF 24HR ENTRY AND SITE SECURITY. | | | | | | | | | | | | 3) IT APPEARS THAT THE FENCE WILL RESTIRCT ACCESS TO | | | FIRE HYDRANTS. | | | | | | FIRE HYDRANTS SHALL BE ACCESSIBLE FROM THE RAODWAY AT | | | ALL TIMES. | | | | | | PLEASE PROVIDE DETAILS AND LOCATIONS OF ALL FIRE | | | HYDRANTS AND PROVIDE FOR ACCESS. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|