| Date |
Text |
| 2020-02-11 07:42:40 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19101152 |
| | ADD: 300 CLEMATIS ST. 1ST FLOOR SUITE |
| | CONT: BUILTMORE CONTRACTING/ CBC |
| | TEL: 561-331-1476 |
| | E-MAIL: INFO: BUILTMORECONTRACTING.COM |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | PLAN |
| | REVIEW COMMENTS |
| | 4TH REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED. |
| | |
| | 2E) (ADDITIONAL INFORMATION REQUIRED. SUBMIT A LETTER |
| | FROM THE DESIGNER OF RECORD LISTING THE SPECIFIC |
| | STRUCTURAL ITEMS THAT WILL BE INSPECTED BY THE SPECIAL |
| | INSPECTOR. NOTE: THE FORMS THAT WERE SUBMITTED ARE |
| | ACCEPTABLE.) THE REQUIRED SPECIAL INSPECTOR |
| | (STRUCTURAL) FORMS HAVE NOT BEEN SUBMITTED. (REPEAT |
| | COMMENT) PER OUR DISCUSSION A SPECIAL INSPECTOR WILL BE |
| | REQUIRED TO INSPECT THE STRUCTURAL WORK FOR THIS |
| | PROJECT. THIS WILL INCLUDE CUTTING AND REPLACING OF THE |
| | SLAB AT THE NEW RAMP AND THE STRUCTURAL STEEL WELDS. |
| | THIS BUILDING AND THE SCOPE OF WORK WILL QUALIFY FOR A |
| | RESIDENT INSPECTOR. WE WILL BE E-MAILING THE LISTED |
| | CONTACT THE GUIDELINES POLICIES AND FORMS TO BE FILED |
| | OUT AND RETURNED TO THE BUILDING DEPARTMENT FOR REVIEW |
| | AND APPROVAL. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION. |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | FORMS WERE E-MAILED TO: BUILTMORECONTRACTING.COM SENT: |
| | 9:08 AM WED. OCT. 30/2019 |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. A SPECIAL INSPECTOR IS REQUIRED TO MONITOR |
| | THIS WORK. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) COMPLIED. |
| | |
| | 10A) COMPLIED. |
| | |
| | 10C) COMPLIED. |
| | |
| | 10D) COMPLIED. |
| | |
| | 10E) N/A |
| | |
| | 11) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) COMPLIED. |
| | |
| | 14) COMPLIED. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) COMPLIED. |
| | |
| | NEW COMMENTS. |
| | |
| | 17) (THE LIMITATIONS FOR THE HYDRO BAN WATERPROOFING |
| | STATE THAT IT IS NOT TO BE USED AS A PRIMARY ROOFING |
| | MEMBRANE OVER OCCUPIED SPACE. THERE IS OCCUPIED SPACE |
| | BELOW THIS AREA.) SUBMIT TWO SETS OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| | LIQUID WATER-PROOFING MATERIAL THAT WILL BE USED AT THE |
| | EXTERIOR ADA RAMP. FBC 107.2.1.2 |
| | |
| | 18) COMPLIED. |
| | |
| | 19) COMPLIED. |
| | |
| | 20) COMPLIED. |
| | |
| | 21) COMPLIED. |
| | |
| | 22) (THE DOCUMENTS THAT WERE SUBMITTED WERE DIGITALLY |
| | SIGNED. ONLY ELECTRONICALLY SUBMITTED PLANS ARE ALLOWED |
| | TO BE SIGNED DIGITALLY. THE PAPER CALCULATION DOCUMENTS |
| | ARE REQUIRED TO BE PHYSICALLY SIGNED, DATED AND SEALED |
| | AS NOTED IN THE ORIGINAL COMMENTS.) THE ORIGINAL |
| | STRUCTURAL CALCULATIONS THAT INCLUDED THE NEW STEEL |
| | BEAM SUPPORTING CONCRETE SLAB, ALUMINUM MULLION DESIGN |
| | AND STAIR INFILL WERE NOT SIGNED, SEALED AND DATED BY |
| | THE ENGINEER AS REQUIRED BY 61G15-23.003. ENGINEERING |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH |
| | MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE |
| | PROVISIONS OF SECTION 471.025, F.S., AND RULE |
| | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED |
| | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL |
| | ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | |
| | 23) COMPLIED. |
| | |
| | 24) AN IMPACT FEE REVIEW IS REQUIRED. SEE IMPACT REVIEW |
| | STOP FOR ADDITIONAL INFORMATION. |
| | |
| | 25) THERE IS AN EXTERIOR FIXED GLASS STOREFRONT PANEL |
| | (S6) SHOWN ON SHEET A102, IN THE WINDOW SCHEDULE ON |
| | SHEET A601 AND THE STRUCTURAL SHEETS. A FRAMED |
| | PARTITION WALL IS SHOWN AT THIS LOCATION IN DETAIL 6 ON |
| | SHEET A401. GLAZING IS NOT ALLOWED IN THIS AREA WHICH |
| | IS AT A 90 DEGREE ANGLE TO THE EXIT PATH FROM THE EXIT |
| | PASSAGEWAY. A FIRE ON THE FIRST FLOOR COULD POTENTIALLY |
| | COMPROMISE THE EXIT. FBC 1023.7 |
| | |
| | 26) THE EXIT DOOR AT THE END OF THE EXIT PASSAGEWAY |
| | APPEARS TO HAVE THE MINIMUM REQUIRED 32" CLEARANCE |
| | BETWEEN THE FACE OF THE OPEN DOOR TO THE OFFSET IN THE |
| | OPPOSITE WALL. THERE IS NO ROOM FOR ERROR WITH THIS |
| | DESIGN. A SUGGESTION WOULD BE TO MOVE THE DOOR FURTHER |
| | INTO THE EXIT PASSAGEWAY AND CHANGE THE DOOR TO SWING |
| | OUT TO THE WALL IN FRONT OF THE SPRINKLER STAND PIPE. |
| | THIS WOULD PROVIDE A BETTER FLOW OF TRAFFIC FROM THE |
| | EXIT PASSAGEWAY AT THE EXIT DISCHARGE. FBC 1010.1.1 & |
| | 1028.1 |
| | |
| | 27) NEW COMMENT. IT HAS BEEN BROUGHT TO MY ATTENTION |
| | THAT ADDITIONAL ACCESSIBLE ENTRANCES TO THIS TENANT |
| | SPACE MAY BE REQUIRED. SECTION 206.4.1 OF THE 2017 |
| | FLORIDA BUILDING CODE ACCESSIBILITY PUBLIC ENTRANCES. |
| | IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH |
| | 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES |
| | SHALL COMPLY WITH 404. THERE ARE THREE PUBLIC ENTRANCES |
| | SHOWN ON THE PLANS. THEREFORE, TWO OF THEM ARE REQUIRED |
| | TO COMPLY WITH 404. IF DOCUMENTATION IS PROVIDED |
| | SHOWING 20 PERCENT DISPROPORTIONALITY TO THE COST OF |
| | THE OVERALL ALTERATION, THEN THE ONE ACCESSIBLE |
| | ENTRANCE MAY MEET THE REQUIREMENTS. SEE FBC |
| | ACCESSIBILITY SECTION 202.4 |
| | |
| | 28) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. ADDITIONAL PLAN REVIEW |
| | COMMENTS MAY BE GENERATED WHEN MORE INFORMATION IS |
| | PROVIDED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |