| 2019-12-31 13:04:22 | BUILDING REVIEW COMMENTS: |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19101085 |
| | ADD: 471 SPENSER AVE. |
| | CONT: ATLANTIC REAL ESTATE & BUILDING |
| | TEL: 561-602-3295 |
| | E-MAIL: [email protected] |
| | |
| | FIRST REVIEW DATE: TUES. NOV. 26/2019 |
| | ACTION: DENIED |
| | |
| | SECOND REVIEW: DECEMBER 31, 2019 |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) OK |
| | |
| | 2A) OK |
| | |
| | 2B) OK |
| | |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD / GROSS |
| | 2 ND REVIEW - PLEASE PROVIDE THE TOTAL OCCUPANT LOAD ON |
| | LIFE SAFETY SHEET BASED OFF THE SQ. FOOTAGE AND B |
| | OCCUPANCY. |
| | GENERAL DATA: |
| | INDICATE IF NON-SPRINKLED |
| | STATE TOTAL AREA UNDER AIR AND TOTAL AREA NEW OUTDOOR |
| | -THIS DATA IS NEEDED BECAUSE IT WILL BE PRINTED ON THE |
| | NEW CERTIFICATE OF OCCUPANCY |
| | |
| | STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | WIND REQUIREMENTS |
| | 2 ND REVIEW ? PLEASE ADJUST WIND CRITERIA TO MATCH FROM |
| | SHEET S-1 AND S-2. THEY SHOW CONFLICTING DATA. |
| | SHEET S-3 IS CORRECT FOR WIND SPEED OF VULT 170 MPH AND |
| | ASD SHOULD 132 MPH. |
| | PLEASE ADJUST SHEET S-3 BUILDING CODE TABLE NUMBER 6 |
| | AND 7. THE DATA SHOULD MATCH THE CONSTRUCTION TYPE |
| | SELECTED. SHEET S-1 STATES VB AND SHEET S-3 STATES 1A. |
| | |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | 2 ND REVIEW - NEW PLANS SHOW PARKING LOT. IS THE |
| | PARKING LOT BEING RE-STRIPED? |
| | THIS WOULD BE UNDER SEPARATE PERMIT AND THE ADA SPOTS |
| | NEED TO SHOW ACCESS AISLE AND ACCESSIBLE ROUTE INTO THE |
| | BUILDING. |
| | |
| | ALSO, REMOVE LANDSCAPE SHEETS AS LANDSCAPING WOULD BE |
| | UNDER A SEPARATE PERMIT. |
| | |
| | 3)-3C) OK |
| | |
| | |
| | 4) SHEET A-3 THE PROPOSED FLOOR PLAN: |
| | 2 ND REVIEW - SHEET A-3 AT DOOR 113 AND 114 SAYS SEE |
| | DETAIL ON D-1. SINCE THERE IS NO D-1, PLEASE UPADTE THE |
| | REFERENCE TO THE DETAIL THAT NUMBER AND SHEET WHERE IT |
| | CAN BE FOUND. |
| | |
| | 4C)- 4G) OK |
| | |
| | 4H) |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | 2 ND REVIEW ? DETAIL OF HOW THE FOUNTAIN MEETS 307 AND |
| | 602 OF ACCESSIBILITY CODE. |
| | ALSO, COMPLY WITH PLUMBING SECTION 410.3 FOR HI-LOW. |
| | |
| | 4I)-4Y) OK |
| | |
| | 4Z) AT THE FRONT ENTRY THE PLAN SHOWS NEW DECORATIVE |
| | 2X2 STUCCO COLUMNS NO DETAILS PROVIDED. 107.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4AA) THE FLOOR PLAN SHOWS A NEW PROPOSED COVERED ENTRY |
| | OF 24?X10?. THE S-1 HAS A FEW DETAILS OF THIS AREA, BUT |
| | THERE ARE (2) COVERED AREA APPROXIMATELY 14?X7? WITH NO |
| | DESIGN CRITERIA OR PLANS PROVIDED FOR THESE AREAS. |
| | 107.2.1.2. CODE COMPLIANCE CANNOT BE REVIEWED FOR THIS |
| | REVIEW CYCLE. |
| | 2 ND REVIEW ? DECORATIVE AWNINGS TO BE SUBMITTED UNDER |
| | SEPARATE PERMIT. PLEASE ADD NOTE AND PROVIDE ALL |
| | ATTACHMENT WITH THAT PERMIT. |
| | |
| | 4BB) SEE ABOVE |
| | |
| | 5)- 6 OK |
| | |
| | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |