| 2019-11-25 15:14:42 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19101085 |
| | 11/25/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: PROVIDE AC EQUIPMENT SCHEDULES ON THE |
| | PLAN- SECTION 107.2.1 WPB & SECTION C403.1 FBC EC. |
| | |
| | 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION C403.2.1 FBC EC. |
| | |
| | 3) M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY |
| | AIR OF THE 5-TON AC SYSTEMS PER SECTION 606.2.1 FBC-M. |
| | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| | MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR |
| | HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF |
| | SUPPLY AIR. PLEASE SHOW THE LOCATIONS OF THE DEVICES |
| | WITH SYMBOLS ON THE PLAN, AND PROVIDE CONTROLS |
| | OPERATION AND SUPERVISORY INFORMATION- SECTIONS 606.4 & |
| | 606.4.1 FBC M. |
| | |
| | 4) M-1: REFER TO SECTION 809.2 FBC EX AND PROVIDE |
| | MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| | SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A SCHEDULE |
| | THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF |
| | OUTDOOR AIR. |
| | |
| | 5) M-1: SHOW HOW VENTILATION AIR (O/A) IS BEING |
| | PROVIDED TO THE OCCUPANTS IN THE OFFICE SPACES- SECTION |
| | 401.2 FBC M. IF USING MECHANICAL VENTILATION, SHOW THE |
| | O/A DUCT RUN AND AIR INLET LOCATIONS WITH REQUIRED |
| | CLEARANCES PER - SECTION 401.4 FBC M. |
| | |
| | 6) M-1: AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR |
| | GRAVITY, SHALL BE PROVIDED FOR O/A DUCTS- SECTION |
| | C403.2.4.3 FBC EC. |
| | |
| | 7) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| | OF THE AC CONDENSERS WITH REQUIRED CLEARANCES, AND |
| | PROVIDE ENGINEERED DETAILS FOR INSTALLATIONS. IF ROOF |
| | STANDS ARE TO BE USED, SUBMIT A FL. PRODUCT APPROVAL, |
| | OR MIAMI-DADE NOA. |
| | |
| | 8) REFER TO SECTION C103.1.1.1.2 FBC EC: THE ARCHITECT |
| | SHALL PROVIDE HIS REGSITRATION NUMBER ON THE |
| | CERTIFICATIONS PAGE 4 OF THE ENERGYGAUGE COMPLIANCE |
| | REPORT. |
| | |
| | 9) THE COMPLIANCE DATA IN THE ENERGYGAUGE REPORT |
| | INDICATES TWO 3-TON SYSTEMS IN THE SOUTH, HOWEVER THE |
| | PLA N INDICATS ONE 5-TON SYSTEM. PLEASE CORRECT- SCTION |
| | 107.2.1 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |