| 2019-10-31 15:24:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET T 1 - THERE IS AN INDICATION OF AAN OCCUPANCY |
| | CLASS AS BUSINESS. |
| | |
| | BISINESS MAY HAVE BEEN THE EXISTING; HOWEVER, THE NEW |
| | OCCUPANCY APPEARS TO BE ASSEMBLY. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS. |
| | |
| | |
| | 2) IF # 1 IS ASSEMBLY THAN A A CHANGE OF OCCUPANY SHALL |
| | BE INDICATED. |
| | |
| | PLEASE PROVIDE IF THE CHANGE OF OCCUPANCY IS |
| | APPLICABLE. |
| | |
| | |
| | |
| | 3) SHEET LS 1 - THE ARE NO INDICATIONS SOF OCCUPANCY |
| | LOAD AND THE DISTRIBUTION TO THE EXITS TO ENSURE THE |
| | EXITS CAN HANDLE THE PROPOSED OCCUPANCY LOAD. |
| | |
| | PER NFPA 101 |
| | |
| | 7.3 CAPACITY OF MEANS OF EGRESS. |
| | 7.3.1 OCCUPANT LOAD. |
| | 7.3.1.1 SUFFICIENT CAPACITY. |
| | 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR |
| | ANY STORY, |
| | BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE |
| | SUFFICIENT FOR THE |
| | OCCUPANT LOAD THEREOF. |
| | |
| | 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| | BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| | NUMBER OF |
| | PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED |
| | TO THAT USE |
| | BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED |
| | IN TABLE |
| | 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B). |
| | WHERE BOTH |
| | GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME |
| | OCCUPANCY, |
| | CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| | FIGURE TO THE |
| | GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO |
| | THE USE FOR |
| | WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY |
| | APPLYING THE NET |
| | AREA FIGURE TO THE NET AREA OF THE PORTION OF THE |
| | BUILDING DEVOTED TO |
| | THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 4) SHEET LS 1 - IS IT THE INTENTION TO LATER SUBDIVIDE |
| | THE SPACE? IF SO, THERE MAY NOT BE SUFFICIENT EXIT |
| | LOCATION TO ALLOW FOR THREE SEPARATE SPACES. |
| | |
| | PLEASE REIVEW AND PROVIDE DETAILS |
| | |
| | |
| | |
| | 5) SHEET LS 1 & E 1 - THERE ARE INDICATIONS OF EXIT & |
| | EMERGENCY LIGHTS ON LS 1; HOWEVER, THE E 1 SHEET DOES |
| | NOT INDICATE THEM. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | 6) SHEET LS 1 - THERE ARE INDICATIONS OF TWO KITCHENS; |
| | HOWEVER, THERE IS NO EQUIPMENT INDICATED. |
| | |
| | PLEASE PROVIDE DETAILS AND/OR JUSTIFY. |
| | |
| | |
| | 7) THERE ARE NO INDICATIONS OF A DOOR SCHDULE INCLUDING |
| | BUT NOT LIMITED EXIT HARDWARE/HANDLES/ LOCKS/LATCHES. |
| | |
| | 7.2 MEANS OF EGRESS COMPONENTS. |
| | 7.2.1 DOOR OPENINGS. |
| | 7.2.1.1 GENERAL. |
| | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| | CONFORM TO |
| | THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE |
| | SPECIAL |
| | REQUIREMENTS OF 7.2.1. |
| | |
| | PLEASE PROVIDE THE INDICATED DOOR SCHEDULE WITH |
| | HARDWARE THAT IS APPLICABLE TO THE OCCUPANCY. |
| | |
| | |
| | 8) THERE ARE NO INDICATION OF THE NEW OCCUPANCY CLASS, |
| | AND FIRE SPRINKLER AND FIRE ALARM MAY BE REQUIRED, IF |
| | ASSEMBLY, NFPA 101 CHAPTER 12 APPLIES. |
| | |
| | 12.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 12.3.5.1 THE WHERE THE OCCUPANT LOAD EXCEEDS 100, THE |
| | FOLLOWING |
| | ASSEMBLY OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY |
| | AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH 9.7.1.1(1): |
| | (1) DANCE HALLS |
| | (2) DISCOTHEQUES |
| | (3) NIGHTCLUBS |
| | (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING |
| | |
| | 12.3.5.2 ANY BUILDING CONTAINING ONE OR MORE ASSEMBLY |
| | OCCUPANCIES WHERE THE AGGREGATE OCCUPANT LOAD OF THE |
| | ASSEMBLY |
| | OCCUPANCIES EXCEEDS 300 SHALL BE PROTECTED BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION |
| | 9.7 AS FOLLOWS (SEE ALSO 12.1.6, 12.2.6, 12.3.2, AND |
| | 12.3.6): |
| | (1) THROUGHOUT THE STORY CONTAINING THE ASSEMBLY |
| | OCCUPANCY |
| | (2) THROUGHOUT ALL STORIES BELOW THE STORY CONTAINING |
| | THE |
| | ASSEMBLY OCCUPANCY |
| | (3) IN THE CASE OF AN ASSEMBLY OCCUPANCY LOCATED BELOW |
| | THE LEVEL |
| | OF EXIT DISCHARGE, THROUGHOUT ALL STORIES INTERVENING |
| | BETWEEN |
| | THAT STORY AND THE LEVEL OF EXIT DISCHARGE, INCLUDING |
| | THE LEVEL |
| | OF EXIT DISCHARGE |
| | |
| | 12.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 12.3.4.1 GENERAL. |
| | 12.3.4.1.1 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF |
| | MORE |
| | THAN 300 AND ALL THEATERS WITH MORE THAN ONE |
| | AUDIENCE-VIEWING |
| | ROOM SHALL BE PROVIDED WITH AN APPROVED FIRE ALARM |
| | SYSTEM IN |
| | ACCORDANCE WITH 9.6.1 AND 12.3.4, UNLESS OTHERWISE |
| | PERMITTED BY |
| | 12.3.4.1.2. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |