| 2019-11-26 10:54:41 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19101085 |
| | ADD: 471 SPENSER AVE. |
| | CONT: ATLANTIC REAL ESTATE & BUILDING |
| | TEL: 561-602-3295 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. NOV. 26/2019 |
| | ACTION: DENIED |
| | |
| | 1A) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED |
| | ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, |
| | STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF |
| | ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF |
| | HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT |
| | NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL |
| | INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE |
| | FOUND ON THEIR WEBSITE: |
| | |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| | RENOVATION.HTML |
| | |
| | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO |
| | [email protected]. THE INFORMATION SHOULD BE IN PDF |
| | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
| | |
| | 1B) PLEASE NOTE AT TIME OF PERMIT APPLICATION THERE WAS |
| | NO ROOFING CONTRACTOR SIGNED ON. THE CGC IS CURRENTLY |
| | NOT LICENSED AS ROOFING CONTRACTOR BUT IS ELIGIBLE FOR |
| | EXAM, APPLICATION IN PROGRESS. |
| | |
| | 1C) NOTICE ONLY, SUB-CONTRACTORS TO PAY THEIR PORTION |
| | OF THE SUB-PERMIT VALUES LISTED FOR EACH SUB-PERMIT. |
| | |
| | 1D) PLEASE NOTE THE ARCHITECTS SEAL IS ENLARGED LARGER |
| | THAN THE FLORIDA ADMINISTRATIVE CODE ALLOWS. ARCHITECT. |
| | 61G1-16.002(1) BOTH SEALS SHALL BE APPROXIMATELY 2" IN |
| | DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES |
| | SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA? |
| | AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT?. |
| | |
| | 1E) THE ARCHITECTS SIGNATURE IS A COPY NOT AN ORIGINAL |
| | SIGNATURE. FL ADMIN CODE 61G16.003(1) ARCHITECTS. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE |
| | ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST |
| | AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC |
| | 61G1-16.003. |
| | |
| | |
| | 2A) SHEET 002 IS INDICATED IN THE TITLEBLOCK AS THE |
| | LIFE SAFETY PLAN WHEREAS IN THE GRAPHICS THE PLAN |
| | STATES IT IS THE FIRE PROTECTION PLAN, WHICH IS IT? IF |
| | THE PLAN IS THE FIRE PROTECTION PLAN SHOWING, NEW FIRE |
| | SPRINKLER SYSTEM, OR AN EXISTING FIRE SPRINKLER SYSTEM, |
| | OR A RECONFIGURED FIRE SPRINKLER SYSTEM? WITH THE |
| | EXISTING WALL SYSTEM IN PLACE, THE FIRE SPRINKLER |
| | LAYOUT WOULDN?T HAVE HAD PROPER COVERAGE. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1OF THE ADMINISTRATIVE CODE |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2B) SHEET 002 IS INDICATED IN THE TITLEBLOCK AS THE |
| | LIFE SAFETY PLAN WHEREAS IN THE GRAPHICS THE PLAN |
| | STATES IT IS THE FIRE PROTECTION PLAN. IF THE PLAN IS |
| | TO BE THE LIFE SAFETY PLAN THEN THERE IS REQUIRED |
| | INFORMATION MISSING ON THE PLAN. |
| | |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1OF THE ADMINISTRATIVE CODE 107.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED 2017 |
| | FBC-B TABLE 504.3, TABLE 504.4 AND TABLE 506.2. |
| | |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD / GROSS |
| | MEANS OF EGRESS |
| | EXIT |
| | EXIT DISCHARGE |
| | MAXIMUM COMMON PATH OF TRAVEL |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | |
| | STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | WIND REQUIREMENTS |
| | NEW BUILDING ENVELOPE REQUIREMENTS |
| | |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | PARKING/ ACCESS AISLE |
| | |
| | 3) DEMO PLAN: |
| | 3A) PALM BEACH COUNTY GEO MAPPING/ GOOGLE MAPS SHOWS |
| | THERE IS 3 INDIVIDUAL BUILDINGS WITH 2 BREEZE WAYS AND |
| | ONE COVERED ROOF SYSTEM OVER THE WHOLE BUILDING. WITHIN |
| | THE BREEZEWAYS IT WOULD APPEAR THE WALLS WOULD BE CBS |
| | BEARING WALLS. THE INTERIOR DEMO FLOOR PLAN IT WOULD |
| | APPEAR THAT 57 % OF THE BEARING WALLS ARE PROPOSED TO |
| | BE REMOVED. SHEET 004 INDICATES PRE-STRESSED CONCRETE, |
| | ROOF TRUSSES W/ CONCRETE DECK. PLEASE CLARIFY NOTE. |
| | WHAT TYPE OF ROOF FRAMING IS THERE, BAR JOIST, WOOD OR |
| | METAL TRUSSES, WHICH WAY DO THEY RUN AND WHAT TYPE OF |
| | ROOF DECK, IS THERE A B-DECK WITH ROOF TOP INSULATION, |
| | B-DECK WITH LIGHT WEIGHT CONCRETE, A PRE-STRESSED |
| | CONCRETE DECK, OR POURED CONCRETE DECKING SYSTEM? SHEET |
| | A-3 DOES SHOW 4 AREAS WHERE A 12X8 INCH PIER IS TO BE |
| | INSTALLED? IS THE PIER GOING TO HAVE A COLUMN PLACED ON |
| | TOP OF THE PIER? THERE IS NO INFORMATION AS TO THE NEW |
| | PIER WILL REQUIRE A FOUNDATION, NOR WHAT THE PIER IS TO |
| | BE CONSTRUCTED FROM? |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED, BEFORE |
| | THE REMOVAL OF THE BREEZEWAY WALLS, WALLS MAYBE BEARING |
| | WALLS, ADDITIONAL STEEL MAYBE REQUIRED BEFORE THE WALL |
| | COULD BE REMOVED. |
| | |
| | 3B)(1) PALM BEACH COUNTY GEO MAPPING/ GOOGLE MAPS SHOWS |
| | THERE IS 3 INDIVIDUAL BUILDINGS WITH 2 BREEZE WAYS AND |
| | ONE COVERED ROOF SYSTEM OVER THE WHOLE BUILDING. SHEET |
| | A-3 THE PROPOSED FLOOR PLAN SHOWS A NEW WINDOW/ DOOR |
| | OPINING (10?X8?) THIS OPENING IS NOT SHOWN ON THE DEMO |
| | PLAN. AGAIN DEPENDING ON WHICH WAY THE ROOF FRAMING |
| | MEMBERS ARE RUNNING ADDITIONAL RE-ENFORCING MAYBE |
| | REQUIRED OVER THE OPENING AT THE BEAM LEVEL.107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3B)(2) THIS SAME PROPOSED NEW WINDOW/ DOOR OPENING THE |
| | STRUCTURAL PLANS DO NOT INDICATE THE NEED FOR VERTICAL |
| | RE-ENFORCEMENT ON BOTH SIDES OF THE DOORWAY. THIS WOULD |
| | BE PART OF THE MWFRS (MAIN WIND FORCE RESISTING |
| | SYSTEM). 2017 FBC-B SECTION 2103.4 METAL REINFORCEMENT. |
| | MASONRY CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS |
| | OF SECTIONS 2104.1.1 AND 2104.1.2 AND WITH TMS 602/ACI |
| | 530.1/ASCE 6. |
| | |
| | 3C) THE DEMO PLAN ALSO INDICATES TO ENCLOSE (4) |
| | SKYLIGHTS WITH 2X6 JOIST AND METAL DECKING. THE |
| | STRUCTURAL SHEET S-1 DOES NOT HAVE ANY INFORMATION ON |
| | THE ROOF FRAMING MEMBERS, SECTION, THICKNESS, JOIST |
| | SPACING, ALLOWABLE ROOF LIVE LOADS AND DEAD LOADS, |
| | ANCHORING TO THE EXISTING ROOF FRAMING AND THE TYPE OF |
| | ROOF DECKING GAUGE AND ANCHORING OF THE DECK TO ROOF |
| | FRAMING MEMBERS. THE PLAN DOES NOT PROVIDE WHAT TYPE OF |
| | DECKING WILL BE ABOVE THE B DECK. 2017 FBC-B 2211.5 |
| | ROOF SYSTEM DESIGN. STEEL BAR JOIST SHALL COMPLY WITH |
| | 2207.2 DESIGN OF THE 2017 FBC-B. |
| | |
| | 4) SHEET A-3 THE PROPOSED FLOOR PLAN: |
| | 4A) FOR BOTH THE INFILL OF THE BREEZEWAY THE PLANS CALL |
| | OUT THE USE OF A DOUBLE 2X10 ABOVE WINDOWS AND WINDOW/ |
| | DOOR WAY. SIMPSON STRONG TIE HANGER HUC2-210 DOUBLE 2 |
| | INCH BY 10 INCH CONCEALED FACE MOUNT HANGER. THE PLANS |
| | DO NOT PROVIDE A DETAIL IF THE HEADER IS TO GO TIGHT TO |
| | THE CONCRETE BEAM, ASSUMED YES. IF SO WHEN THE |
| | CONCEALED FACE HANGER IS ANCHORED TO THE CMU UNITS HOW |
| | ARE THE HEADERS GOING TO BE PUT INTO THE CONCEALED FACE |
| | HANGER, THERE IS NO ROOM TO INSTALL THE 2X10S? |
| | 107.2.1.2 ADDITIONAL INFORMATION AS TO HOW THE PROCESS |
| | WILL OCCUR. |
| | |
| | 4B) THE SAME OPENING DEPICTED WITH THE USE OF A DOUBLE |
| | 2X10, CONCEALED HANGERS FOR THE NEW FRONT DOOR ENTRY. |
| | THE PLANS STATE THIS WILL BE A 10 FOOT WIDE OPENING |
| | WHEREAS THE OTHER 4 OPENINGS ARE A 7 FOOT 4 INCH |
| | OPENING. THE PLANS ARE SILENT AS TO HOW THE HEADER IS |
| | TO BE ANCHORED MIDPOINT FOR HORIZONTAL DEFLECTION, THIS |
| | SYSTEM IS TO BE PART OF THE MAIN WIND FORCE RESISTING |
| | SYSTEM? |
| | |
| | 2017 FBC-B 1604.8.2 STRUCTURAL WALLS. WALLS THAT |
| | PROVIDE VERTICAL LOAD-BEARING RESISTANCE OR LATERAL |
| | SHEAR RESISTANCE FOR A PORTION OF THE STRUCTURE SHALL |
| | BE ANCHORED TO THE ROOF AND TO ALL FLOORS AND MEMBERS |
| | THAT PROVIDE LATERAL SUPPORT FOR THE WALL OR THAT ARE |
| | SUPPORTED BY THE WALL. THE CONNECTIONS SHALL BE CAPABLE |
| | OF RESISTING THE HORIZONTAL FORCES SPECIFIED IN SECTION |
| | 1.4.5 OF ASCE 7 FOR WALLS OF STRUCTURES ASSIGNED TO |
| | SEISMIC DESIGN CATEGORY A AND TO SECTION 12.11 OF ASCE |
| | 7 FOR WALLS OF STRUCTURES ASSIGNED TO ALL OTHER SEISMIC |
| | DESIGN CATEGORIES. REQUIRED ANCHORS IN MASONRY WALLS OF |
| | HOLLOW UNITS OR CAVITY WALLS SHALL BE EMBEDDED IN A |
| | REINFORCED GROUTED STRUCTURAL ELEMENT OF THE WALL. SEE |
| | SECTIONS 1609 FOR WIND DESIGN REQUIREMENTS AND 1613 FOR |
| | EARTHQUAKE DESIGN REQUIREMENTS. |
| | |
| | 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND |
| | THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| | STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| | GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| | SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | THE TOTAL LATERAL FORCE SHALL BE DISTRIBUTED TO THE |
| | VARIOUS VERTICAL ELEMENTS OF THE LATERAL |
| | FORCE-RESISTING SYSTEM IN PROPORTION TO THEIR |
| | RIGIDITIES, CONSIDERING THE RIGIDITY OF THE HORIZONTAL |
| | BRACING SYSTEM OR DIAPHRAGM. RIGID ELEMENTS ASSUMED NOT |
| | TO BE A PART OF THE LATERAL FORCE-RESISTING SYSTEM ARE |
| | PERMITTED TO BE INCORPORATED INTO BUILDINGS PROVIDED |
| | THEIR EFFECT ON THE ACTION OF THE SYSTEM IS CONSIDERED |
| | AND PROVIDED FOR IN THE DESIGN. A DIAPHRAGM IS RIGID |
| | FOR THE PURPOSE OF DISTRIBUTION OF STORY SHEAR AND |
| | TORSIONAL MOMENT WHEN THE LATERAL DEFORMATION OF THE |
| | DIAPHRAGM IS LESS THAN OR EQUAL TO TWO TIMES THE |
| | AVERAGE STORY DRIFT. WHERE REQUIRED BY ASCE 7, |
| | PROVISIONS SHALL BE MADE FOR THE INCREASED FORCES |
| | INDUCED ON RESISTING ELEMENTS OF THE STRUCTURAL SYSTEM |
| | RESULTING FROM TORSION DUE TO ECCENTRICITY BETWEEN THE |
| | CENTER OF APPLICATION OF THE LATERAL FORCES AND THE |
| | CENTER OF RIGIDITY OF THE LATERAL FORCE RESISTING |
| | SYSTEM. |
| | |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS, SECTION 1610 FOR LATERAL SOIL LOADS AND SECTION |
| | 1613 FOR EARTHQUAKE LOADS. |
| | 4C) THE FLOOR PLAN DOES NOT PROVIDE A DETAIL FOR THE |
| | PROPOSED KITCHEN, NOT A BREAK AREA. PLEASE NOTE WITH |
| | THE DESIGNATION OF A KITCHEN THE MEANS OF EGRESS |
| | THROUGH A KITCHEN IS PROHIBITED. PLEASE REVIEW SECTION |
| | 1016.2.(5) EGRESS SHALL NOT PASS THROUGH KITCHENS, |
| | STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR |
| | PURPOSES. |
| | |
| | 4D) THE FLOOR PLAN DOES NOT INDICATE IF ANY AND OR ALL |
| | OF THE MEANS OF EGRESS ARE AN ACCESSIBLE ENTRY. PLEASE |
| | SHOW COMPLIANCE WITH; |
| | 2017 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES. |
| | (DOORWAYS) |
| | IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH |
| | 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES |
| | SHALL COMPLY WITH 404. BARRIERS AT COMMON OR EMERGENCY |
| | ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS |
| | CONDUCTING BUSINESS WITH THE GENERAL PUBLIC THAT ARE |
| | EXISTING, UNDER CONSTRUCTION, OR UNDER CONTRACT FOR |
| | CONSTRUCTION WHICH WOULD PREVENT A PERSON FROM USING |
| | SUCH ENTRANCES OR EXITS SHALL BE REMOVED. |
| | |
| | 4E) 2 ACCESSIBLE MEANS OF EGRESS REQUIRED. 2017 ACCESS. |
| | CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES |
| | REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60 |
| | PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404. |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 4F) SIGNAGE 2017 FBC-ACCESSIBILITY CODE SECTION 216.6 |
| | ENTRANCES. WHERE NOT ALL ENTRANCES COMPLY WITH 404, |
| | ENTRANCES COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE |
| | INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH |
| | 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT |
| | INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING |
| | WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT |
| | COMPLY WITH 404. |
| | |
| | 4G) PLEASE PROVIDE A DETAIL OF THE KITCHEN CABINETS, |
| | COUNTER HEIGHT, IF THERE IS A SINK AND ASSOCIATED |
| | APPLIANCES. ACCESSIBILITY REQUIREMENTS CANNOT BE |
| | DETERMINED AT THIS TIME. NO INFORMATION WAS PROVIDED. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4H) THE FLOOR PLAN IS MISSING THE REQUIRED DRINKING |
| | FOUNTAIN IN COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY |
| | CODE SECTION 211.2 MINIMUM NUMBER. NO FEWER THAN TWO |
| | DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | |
| | 4I) THE FLOOR PLAN SHOWS 6 NEW UNISEX RESTROOMS BUT |
| | THERE IS NO DETAIL OF THE UNISEX AND OR ACCESSIBLE |
| | RESTROOMS. COMPLIANCE WITH THESE ACCESSIBILITY |
| | REQUIREMENTS CANNOT BE ACHIEVED. |
| | WATER CLOSET. |
| | 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 4J) 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE |
| | WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER |
| | CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY |
| | NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE |
| | ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT |
| | OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER |
| | FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE |
| | REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 4K) 606 LAVATORIES AND SINKS. |
| | 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR SPACE. A |
| | CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A |
| | FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. |
| | EXCEPTIONS: |
| | 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE |
| | PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK |
| | TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET |
| | BARS. |
| | |
| | 4L) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4M) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS |
| | FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED |
| | METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS |
| | MINIMUM. |
| | |
| | 4N) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND |
| | SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES |
| | AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| | ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. |
| | |
| | 4O) MIRRORS. 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 4P) GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE |
| | SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE. |
| | |
| | 4Q) 2017 ACCESSIBILITY CODE 604.5.2 REAR WALL. THE REAR |
| | WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM |
| | AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| | INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610 |
| | MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | |
| | |
| | 4R) TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE |
| | 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY |
| | WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| | CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED |
| | BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE |
| | THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW |
| | CONTINUOUS PAPER FLOW. |
| | |
| | 4S) THE FLOOR PLAN SHOWS 4 NEW 4X3 FOOT SKYLIGHTS. |
| | PLEASE NOTE THE PROPOSED NEW SKYLIGHTS ARE NOT |
| | REFLECTED ON THE ROOF TOP PLAN. PLEASE PROVIDE |
| | INFORMATION ON THE CUTTING IN OF THE SKYLIGHT, IF THERE |
| | IS ADDITIONAL FRAMING REQUIRED FOR THE SKYLIGHT. |
| | WITHOUT HAVING ANY INFORMATION ON THE SKYLIGHT, PLEASE |
| | PROVIDE THE PRODUCT APPROVAL SHOWING THE MOUNTING OF |
| | THE SKYLIGHT, LARGE MISSILE IMPACT TESTING AND |
| | ASSOCIATED PRESSURES FOR THE SKYLIGHT. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4T) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 4U) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 4V) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 4W) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 4X) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 4Y) PLEASE NOTE THE WIND DESIGN CRITERIA IS NOT GIVEN |
| | FOR THE ENCLOSED BUILDING. NOR IS THE ASSOCIATED |
| | PRESSURES FOR ZONES 1,2,3,4 & 5. PLEASE PROVIDE |
| | COMPLIANCE WITH 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 4Z) AT THE FRONT ENTRY THE PLAN SHOWS NEW DECORATIVE |
| | 2X2 STUCCO COLUMNS NO DETAILS PROVIDED. 107.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4AA) THE FLOOR PLAN SHOWS A NEW PROPOSED COVERED ENTRY |
| | OF 24?X10?. THE S-1 HAS A FEW DETAILS OF THIS AREA, BUT |
| | THERE ARE (2) COVERED AREA APPROXIMATELY 14?X7? WITH NO |
| | DESIGN CRITERIA OR PLANS PROVIDED FOR THESE AREAS. |
| | 107.2.1.2. CODE COMPLIANCE CANNOT BE REVIEWED FOR THIS |
| | REVIEW CYCLE. |
| | |
| | 4BB) THE FLOOR PLAN ALSO INDICATES THERE ARE (2) 4?X12? |
| | STRUCTURAL AWNINGS. NO DESIGN CRITERIA OR PLANS |
| | PROVIDED FOR THESE AREAS. 107.2.1.2. CODE COMPLIANCE |
| | CANNOT BE REVIEWED FOR THIS REVIEW CYCLE. |
| | 5) SHEET S-1: |
| | 5A) THE PLAN SHOWS FOOTINGS AND SIMPSON STRONG-TIE |
| | ABU66Z POST BASE BUT THERE IS NO MENTION OF THE ANCHOR |
| | TO BE USED TO ANCHOR THE POST BASE TO THE FOUNDATION. |
| | PART OF THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM) |
| | PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE POST BASE. |
| | |
| | 5B) THE ELEVATION SHOW THE POST TO BE A 6X6 LVL WOOD |
| | POST. THE PLANS DO NOT INDICATE WHERE POST BASE IS IN |
| | RELATION TO GRADE, AND IF THE END OF THE WOOD LVL IS IN |
| | COMPLIANCE WITH THE 2017 FBC-B SECTIONS: |
| | 2304.12.2 OTHER LOCATIONS. WOOD USED IN THE LOCATIONS |
| | SPECIFIED IN SECTIONS 2304.12.2.1 THROUGH 2304.12.2.5 |
| | SHALL BE NATURALLY DURABLE WOOD OR PRESERVATIVE-TREATED |
| | WOOD IN ACCORDANCE WITH AWPA U1. PRESERVATIVE-TREATED |
| | WOOD USED IN INTERIOR LOCATIONS SHALL BE PROTECTED WITH |
| | TWO COATS OF URETHANE, SHELLAC, LATEX EPOXY OR VARNISH |
| | UNLESS WATER-BORNE PRESERVATIVES ARE USED. PRIOR TO |
| | APPLICATION OF THE PROTECTIVE FINISH, THE WOOD SHALL BE |
| | DRIED IN ACCORDANCE WITH THE MANUFACTURER?S |
| | RECOMMENDATIONS. |
| | 2304.12.2.2 POSTS OR COLUMNS. POSTS OR COLUMNS |
| | SUPPORTING PERMANENT STRUCTURES AND SUPPORTED BY A |
| | CONCRETE OR MASONRY SLAB OR FOOTING THAT IS IN DIRECT |
| | CONTACT WITH THE EARTH SHALL BE OF NATURALLY DURABLE OR |
| | PRESERVATIVE-TREATED WOOD. |
| | EXCEPTION: POSTS OR COLUMNS THAT ARE NOT EXPOSED TO THE |
| | WEATHER, ARE SUPPORTED BY CONCRETE PIERS OR METAL |
| | PEDESTALS PROJECTED AT LEAST 1 INCH (25 MM) ABOVE THE |
| | SLAB OR DECK AND 8 INCHES (203 MM) ABOVE EXPOSED EARTH |
| | AND ARE SEPARATED BY AN IMPERVIOUS MOISTURE BARRIER. |
| | |
| | 5C) THE PORTICO ELEVATION IT WOULD APPEAR TO HAVE A |
| | RAISED WOOD DECK WHEREAS SHEET A-3 INDICATES A PORTICO |
| | WITH PAVER DECK. 107.2.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. DISCREPANCY IN PLANS. |
| | |
| | 6) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED |
| | ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, |
| | STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF |
| | ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF |
| | HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT |
| | NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL |
| | INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE |
| | FOUND ON THEIR WEBSITE: |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| | RENOVATION.HTML |
| | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO |
| | [email protected]. THE INFORMATION SHOULD BE IN PDF |
| | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
| | |
| | 7) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN |
| | SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND |
| | REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE |
| | THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW |
| | PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |