Plan Review Notes
Plan Review Notes For Permit 19101071
Permit Number 19101071
Review Stop P
Sequence Number 1
Notes
Date Text
2019-11-13 06:23:59PLUMBING 1ST REVIEW**DENIED**19101071
  
 1) PROVIDE ISOMETRIC DRAWING FOR ALL NEW PLUMBING WORK
 UNDER THE SCOPE OF THIS PERMIT. FBC 107.3.5
 2) PROVIDE SHOWER PAN DETAIL CALLING OUT MATERIAL TO BE
 USED AND PRE-PITCHING OF FLOOR MIN 2%. FBCR P2709.2,
 P2709.3
 3) SHOWER SHOW 2 HANDLE SHOWER VALVE. PROVIDE
 INSTALLATION MANUAL SHOWING VALVE COMPLIES WITH
 FBCR-P2708.4 BY BEING ASSE 1016 APPROVED.
 TIM HUNT
 PLUMBING PLANS EXAMINER