| 2019-10-23 09:57:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | A SITE REVIEW WAS CONDUCTED AND FOUND THE FOLLOWING |
| | WHICH IS NOT ADDRESS NOR INDICATED ON THE SUBMITTED |
| | PLAN SETS: |
| | |
| | ? PER FLORIDA ACCESSIBILITY CODE AND THE AMERICANS WITH |
| | DISABILITIES ACT (ADA) ALL FACILITIES SHALL BE |
| | ACCESSIBLE TO PERSONS WITH DISABILITIES. THE FLOOR OF |
| | THE BUILDING IS UNEVEN WITH SEVERAL AREAS OF DIFFERENT |
| | TYPES OF FLOORING MATERIALS. THE NORTH ROOM OF THE |
| | BUILDING HAS AREAS THAT ARE FILLED IN WITH PLYWOOD, |
| | SOME AREAS THAT ARE BARE CONCRETE AND OTHERS HAVE |
| | REMNANTS OF MUD SET TILE FLOORING. THERE ARE NUMEROUS |
| | TRIPPING HAZARDS AND THE FLOOR WILL NEED AN EXTENSIVE |
| | AMOUNT OF WORK IN ORDER TO MEET FLORIDA ACCESSIBILITY |
| | REQUIREMENTS FOR AN ACCESSIBLE ROUTE. THE SOUTH PORTION |
| | OF THE BUILDING APPEARS TO BE A NEWER ADDITION AND THE |
| | FLOOR ELEVATION IS APPROXIMATELY 6 TO 8 INCHES HIGHER |
| | THAN THE OLDER NORTH PART. THIS CHANGE IN ELEVATION |
| | WOULD REQUIRE ACCESSIBLE RAMPS. |
| | ? METAL SHORING JACKS. THE ROOF AND CEILING OF THE |
| | FRONT ROOM ARE WOOD FRAME AND THE LARGE WOODEN BEAM |
| | THAT RUNS DOWN THE CENTER OF THE NORTH ROOM IS SHORED |
| | UP WITH METAL SHORING JACKS THIS BEAM HAS EXTENSIVE |
| | TERMITE DAMAGE IN SOME AREAS. SOME OF THE CEILING |
| | JOISTS ALSO HAVE VISIBLE TERMITE DAMAGE. THE PROPOSED |
| | USE OF THE SPACE WITH LOW LIGHT LEVELS, STROBE LIGHTS, |
| | AND DISORIENTING SOUNDS, MAY CAUSE PATRONS TO IMPACT |
| | THE SHORING AND POTENTIALLY CAUSE LATERAL MOVEMENT OF |
| | THE SHORING AND REMOVAL OF SUPPORT FOR THE WOODEN BEAM. |
| | ? FLAME RETARDANT TREATMENT OF CURTAINS. FLAME |
| | RETARDANT TREATMENT CERTIFICATE FOR THE CURTAIN FABRIC |
| | MUST BE PROVIDED TO SHOW THAT THE SPREAD OF FLAME WILL |
| | NOT POSE UNACCEPTABLE RISK TO OCCUPANTS AS THEY LEAVE |
| | THE BUILDING IN AN EMERGENCY. THIS IS THE SAME |
| | REQUIREMENT THAT APPLIES TO TENTS. |
| | ? PLYWOOD PANEL WALLS ATTACHMENT TO CEILING JOISTS. WE |
| | COULD NOT DETERMINE HOW THE 2X4S THAT SUPPORT THE |
| | PLYWOOD PANEL WALLS ARE ATTACHED TO THE CEILING JOISTS. |
| | WE WERE ABLE TO MOVE ONE OF THE WALLS BY PUSHING ON IT |
| | WITH VERY LITTLE FORCE. THE PROPOSED USE OF THE SPACE |
| | WITH LOW LIGHT LEVELS, STROBE LIGHTS, AND DISORIENTING |
| | SOUNDS, MAY CAUSE PATRONS TO IMPACT THE PLYWOOD WALL |
| | PANELS AND POTENTIALLY DETACH THEM FROM THE CEILING |
| | JOISTS AND CAUSE THE WALL PANELS TO FALL. ALSO, THE |
| | CEILING JOISTS WERE NOT INTENDED TO CARRY THE TORQUE |
| | (TWISTING) FORCE OF A 12 FOOT LONG LEVER WITH A PERSON |
| | RUNNING INTO IT. |
| | ? IN THE EVENT OF AN EMERGENCY THE LIGHTING MUST TURN |
| | ON AND PROVIDE SUFFICIENT LIGHTING LEVELS FOR SAFE |
| | EGRESS. THERE ARE ONLY TWO EXISTING FOUR FOOT |
| | FLORESCENT LIGHTING FIXTURES IN THE NORTH ROOM. THEY DO |
| | NOT PROVIDE ADEQUATE LIGHTING FOR THAT AREA. |
| | ? EACH EXIT SHALL BE MARKED BY ILLUMINATED EXIT SIGNS. |
| | THE EXIT LIGHTS ARE NOT FUNCTIONING AT THIS TIME. SOME |
| | WERE JUST HANGING BY THE ELECTRICAL CONNECTION. |
| | ? STORED MATERIALS. THERE ARE SOME MATERIALS STORED IN |
| | THE SOUTH ROOM OF THE BUILDING THAT IS BLOCKING ONE OF |
| | THE EXITS AND EXIT PATHS. |
| | ? CONSTRUCTION SITE. THE BUILDING APPEARS TO BE A |
| | CONSTRUCTION SITE RATHER THAN A SHELL BUILDING READY |
| | FOR OCCUPANCY. |
| | ? PLAN REVIEW. PLEASE ADDRESS ALL PLAN REVIEW COMMENTS |
| | ENTERED UNDER PERMIT APPLICATION # 19101052. |
| | |
| | |
| | 1) THIS EVENT/BUILDING IS DEFINED IN THE FLORIDA FIRE |
| | PREVENTION CODE AS A SPECIAL AMUSEMENT BUILDING AND AN |
| | ASSEMBLY OCCUPANCY: |
| | |
| | 3.3.29.10* SPECIAL AMUSEMENT BUILDING. A BUILDING THAT |
| | IS |
| | TEMPORARY, PERMANENT, OR MOBILE AND CONTAINS A DEVICE |
| | OR |
| | SYSTEM THAT CONVEYS PASSENGERS OR PROVIDES A WALKWAY |
| | ALONG, |
| | AROUND, OR OVER A COURSE IN ANY DIRECTION AS A FORM OF |
| | AMUSEMENT ARRANGED SO THAT THE EGRESS PATH IS NOT |
| | READILY |
| | APPARENT DUE TO VISUAL OR AUDIO DISTRACTIONS OR AN |
| | INTENTIONALLY |
| | CONFOUNDED EGRESS PATH, OR IS NOT READILY AVAILABLE DUE |
| | TO THE |
| | MODE OF CONVEYANCE THROUGH THE BUILDING OR STRUCTURE. |
| | |
| | 3.3.183.3* ASSEMBLY OCCUPANCY. AN OCCUPANCY (1) USED |
| | FOR A |
| | GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION, |
| | WORSHIP, |
| | ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING |
| | TRANSPORTATION, OR SIMILAR USES; OR (2) USED AS A |
| | SPECIAL |
| | AMUSEMENT BUILDING, REGARDLESS OF OCCUPANT LOAD. |
| | |
| | PER NFPA 1 CH 20 FIRE SPRINKLERS ARE REQUIRED. |
| | |
| | 20.1.4.2* AUTOMATIC SPRINKLERS. EVERY SPECIAL AMUSEMENT |
| | BUILDING, |
| | OTHER THAN BUILDINGS OR STRUCTURES NOT EXCEEDING 10 FT |
| | (3050 MM) IN |
| | HEIGHT AND NOT EXCEEDING 160 FT2 (15 M2) IN AGGREGATE |
| | HORIZONTAL |
| | PROJECTION, SHALL BE PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM INSTALLED AND MAINTAINED IN |
| | ACCORDANCE |
| | WITH SECTION 13.3. |
| | |
| | ADDITIONAL REQUIREMENTS: |
| | |
| | 20.1.4.4 SMOKE DETECTION. WHERE THE NATURE OF THE |
| | SPECIAL |
| | AMUSEMENT BUILDING IS SUCH THAT IT OPERATES IN REDUCED |
| | LIGHTING LEVELS, |
| | THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN |
| | APPROVED AUTOMATIC |
| | SMOKE DETECTION SYSTEM IN ACCORDANCE WITH SECTION 13.7. |
| | [101:12.4.8.4; 101: 13.4.8.4] |
| | 20.1.4.5 ALARM INITIATION. ACTUATION OF ANY SMOKE |
| | DETECTION SYSTEM |
| | DEVICE SHALL SOUND AN ALARM AT A CONSTANTLY ATTENDED |
| | LOCATION ON THE |
| | PREMISES. [101: 12.4.8.5, 101: 13.4.8.5] |
| | 20.1.4.6 ILLUMINATION. ACTUATION OF THE AUTOMATIC |
| | SPRINKLER SYSTEM, |
| | OR ANY OTHER SUPPRESSION SYSTEM, OR ACTUATION OF A |
| | SMOKE DETECTION |
| | SYSTEM HAVING AN APPROVED VERIFICATION OR CROSS-ZONING |
| | OPERATION |
| | CAPABILITY SHALL PROVIDE FOR THE FOLLOWING: |
| | (1) INCREASE IN ILLUMINATION IN THE MEANS OF EGRESS TO |
| | THAT REQUIRED |
| | BY SECTION 14.12 |
| | (2) TERMINATION OF ANY CONFLICTING OR CONFUSING SOUNDS |
| | AND VISUALS |
| | [101: 12.4.8.6; 101: 13.4.8.6] |
| | 20.1.4.7 EXIT MARKING. |
| | 20.1.4.7.1 EXIT MARKING SHALL BE IN ACCORDANCE WITH |
| | SECTION 14.14. |
| | [101: 12.4.8.7.1; 101: 13.4.8.7.1] |
| | 20.1.4.7.2 FLOOR PROXIMITY EXIT SIGNS SHALL BE PROVIDED |
| | IN ACCORDANCE |
| | WITH 14.14.1.6. [101: 12.4.8.7.2; 101: 13.4.8.7.2] |
| | 20.1.4.7.3* IN SPECIAL AMUSEMENT BUILDINGS WHERE MAZES, |
| | MIRRORS, OR |
| | OTHER DESIGNS ARE USED TO CONFOUND THE EGRESS PATH, |
| | APPROVED |
| | DIRECTIONAL EXIT MARKING THAT BECOMES APPARENT IN AN |
| | EMERGENCY SHALL |
| | BE PROVIDED. |
| | |
| | IN AN EFFORT TO CONSIDER ALTERNATIVES TO THE ABOVE |
| | REQUIREMENTS, THE SITE FINDINGS NEED TO BE ADDRESSED |
| | AND CORRECTED. |
| | |
| | |
| | |
| | 2) ADDITIONALLY, PER NFPA 101 CH 7 MEANS OF EGRESS, THE |
| | FLOOR WALKING SERFACE SHALL MEET THE FOLLOWING: |
| | |
| | 7.1.6 WALKING SURFACES IN THE MEANS OF EGRESS. |
| | 7.1.6.1 GENERAL. |
| | 7.1.6.1.1 WALKING SURFACES IN THE MEANS OF EGRESS SHALL |
| | COMPLY |
| | WITH 7.1.6.2 THROUGH 7.1.6.4. |
| | 7.1.6.1.2 APPROVED EXISTING WALKING SURFACES SHALL BE |
| | PERMITTED. |
| | 7.1.6.2 CHANGES IN ELEVATION. ABRUPT CHANGES IN |
| | ELEVATION OF |
| | WALKING SURFACES SHALL NOT EXCEED ? IN. (6.3 MM). |
| | CHANGES IN |
| | ELEVATION EXCEEDING ? IN. (6.3 MM), BUT NOT EXCEEDING ? |
| | IN. (13 |
| | MM), SHALL BE BEVELED WITH A SLOPE OF 1 IN 2. CHANGES |
| | IN ELEVATION |
| | EXCEEDING ? IN. (13 MM) SHALL BE CONSIDERED A CHANGE IN |
| | LEVEL |
| | AND SHALL BE SUBJECT TO THE REQUIREMENTS OF 7.1.7. |
| | 7.1.6.3 LEVEL. |
| | 7.1.6.3.1 WALKING SURFACES SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING: |
| | (1) WALKING SURFACES SHALL BE NOMINALLY LEVEL. |
| | (2) THE SLOPE OF A WALKING SURFACE IN THE DIRECTION OF |
| | TRAVEL SHALL |
| | NOT EXCEED 1 IN 20, UNLESS THE RAMP REQUIREMENTS OF |
| | 7.2.5 ARE |
| | MET. |
| | (3) THE SLOPE PERPENDICULAR TO THE DIRECTION OF TRAVEL |
| | SHALL NOT |
| | EXCEED 1 IN 48. |
| | 7.1.7 CHANGES IN LEVEL IN MEANS OF EGRESS. |
| | 7.1.7.1 CHANGES IN LEVEL IN MEANS OF EGRESS SHALL BE |
| | ACHIEVED BY |
| | AN APPROVED MEANS OF EGRESS WHERE THE ELEVATION |
| | DIFFERENCE |
| | EXCEEDS 21 IN. (535 MM). |
| | 7.1.7.2* CHANGES IN LEVEL IN MEANS OF EGRESS NOT IN |
| | EXCESS OF 21 |
| | IN. (535 MM) SHALL BE ACHIEVED EITHER BY A RAMP |
| | COMPLYING WITH |
| | THE REQUIREMENTS OF 7.2.5 OR BY A STAIR COMPLYING WITH |
| | THE |
| | REQUIREMENTS OF 7.2.2. |
| | 7.1.7.2.1 WHERE A RAMP IS USED TO MEET THE REQUIREMENTS |
| | OF |
| | 7.1.7.2, THE PRESENCE AND LOCATION OF RAMPED PORTIONS |
| | OF WALKWAYS |
| | SHALL BE READILY APPARENT. |
| | 7.1.7.2.2 WHERE A STAIR IS USED TO MEET THE |
| | REQUIREMENTS OF 7.1.7.2, |
| | THE TREAD DEPTH OF SUCH STAIR SHALL BE NOT LESS THAN 13 |
| | IN. (330 MM). |
| | 7.1.7.2.3 TREAD DEPTH IN INDUSTRIAL EQUIPMENT ACCESS |
| | AREAS AS |
| | PROVIDED IN 40.2.5.3 SHALL BE PERMITTED. |
| | 7.1.7.2.4 THE PRESENCE AND LOCATION OF EACH STEP SHALL |
| | BE READILY |
| | APPARENT. |
| | |
| | 3) BASED ON THE ABOVE SITE CONDITIONS AND PROPOSED |
| | AMUSEMENT USE, THE FOLLOWING MEANS OF EGRESS |
| | REQUIRMENTS SHALL BE MET: |
| | |
| | 7.1.9 IMPEDIMENTS TO EGRESS. ANY DEVICE OR ALARM |
| | INSTALLED TO |
| | RESTRICT THE IMPROPER USE OF A MEANS OF EGRESS SHALL BE |
| | DESIGNED |
| | AND INSTALLED SO THAT IT CANNOT, EVEN IN CASE OF |
| | FAILURE, IMPEDE OR |
| | PREVENT EMERGENCY USE OF SUCH MEANS OF EGRESS, UNLESS |
| | OTHERWISE |
| | PROVIDED IN 7.2.1.6 AND CHAPTERS 18, 19, 22, AND 23. |
| | 7.1.10 MEANS OF EGRESS RELIABILITY. |
| | 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE |
| | CONTINUOUSLY |
| | MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO |
| | FULL INSTANT |
| | USE IN THE CASE OF FIRE OR OTHER EMERGENCY. |
| | 7.1.10.2 FURNISHINGS AND DECORATIONS IN MEANS OF |
| | EGRESS. |
| | 7.1.10.2.1 NO FURNISHINGS, DECORATIONS, OR OTHER |
| | OBJECTS SHALL |
| | OBSTRUCT EXITS OR THEIR ACCESS THERETO, EGRESS THERE |
| | FROM, OR |
| | VISIBILITY THEREOF. |
| | 7.1.10.2.2 NO OBSTRUCTION BY RAILINGS, BARRIERS, OR |
| | GATES SHALL |
| | DIVIDE THE MEANS OF EGRESS INTO SECTIONS APPURTENANT TO |
| | INDIVIDUAL |
| | ROOMS, APARTMENTS, OR OTHER OCCUPIED SPACES. WHERE THE |
| | AUTHORITY |
| | HAVING JURISDICTION FINDS THE REQUIRED PATH OF TRAVEL |
| | TO BE |
| | OBSTRUCTED BY FURNITURE OR OTHER MOVABLE OBJECTS, THE |
| | AUTHORITY |
| | SHALL BE PERMITTED TO REQUIRE THAT SUCH OBJECTS BE |
| | SECURED OUT OF |
| | THE WAY OR SHALL BE PERMITTED TO REQUIRE THAT RAILINGS |
| | OR OTHER |
| | PERMANENT BARRIERS BE INSTALLED TO PROTECT THE PATH OF |
| | TRAVEL AGAINST |
| | ENCROACHMENT. |
| | 7.1.10.2.3 MIRRORS SHALL NOT BE PLACED ON EXIT DOOR |
| | LEAVES. MIRRORS |
| | SHALL NOT BE PLACED IN OR ADJACENT TO ANY EXIT IN SUCH |
| | A MANNER AS |
| | TO CONFUSE THE DIRECTION OF EGRESS. |
| | |
| | |
| | PLEASE PROVIDE DETAILS OF EACH MEANS OF EGRESS. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |