| Date |
Text |
| 2020-02-12 14:18:08 | RESIDENTIAL (R3) BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- OK |
| | |
| | 2- SITE SPECIFIC ENGINEERING SUBMITTED FOR THE |
| | ATTACHMENT OF THE SHED: |
| | |
| | A) OK. |
| | |
| | ORIGINAL COMMENT: |
| | B) SITE SPECIFIC ENGINEERING NEEDS TO HAVE THE ORIGINAL |
| | SEAL AND SIGNATURE OF THE ENGINEER AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES WHEN SUBMITTING |
| | DOCUMENTS/PLANS FOR PUBLIC RECORDS. PROVIDE BOTH COPIES |
| | WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NEED ORIGINAL SEAL AND SIGNATURE OF THE |
| | ENGINEER. THIS SITE SPECIFIC ENGINEERING IS NOT PART OF |
| | THE MANUFACTURED BUILDING APPROVED PLANS. THAT IS WHY |
| | SITE SPECIFIC ENGINEERING WITH ENGINEER'S ORIGINAL SEAL |
| | AND SIGNATURE IS REQUIRED. |
| | |
| | ORIGINAL COMMENT: |
| | C) CLEARLY MARK WHICH TIE-DOWN DETAIL IS GOING TO BE |
| | USED. SEC. 107.2.1 CITY AMENDMENTS. |
| | NOTE: BUILDING IS LOCATED IN EXPOSURE D. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. THIS NEEDS TO BE DONE BY THE ENGINEER |
| | RESPONSIBLE FOR THE SITE SPECIFIC ENGINEERING. |
| | |
| | 3- IF THE MANUFACTURED SHED HAVE THE ELECTRICAL |
| | EQUIPMENT SHOWN ON DRAWING 8 OF 8, THEN ELECTRICAL |
| | PERMIT/REVIEW IS REQUIRED FOR THE SITE SPECIFIC |
| | INSTALLATION. . SEC. 105.1 CITY AMENDMENTS. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |