| 2020-02-05 08:16:03 | RESIDENTIAL (R3) SHED SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- MANUFACTURED BUILDING PANS SUBMITTED ARE FOR THE |
| | 2014 BUILDING CODE. NEED TO PROVIDE PLANS FOR APPROVED |
| | MANUFACTURED BUILDING UNDER THE CURRENT 2017 BUILDING |
| | CODE AS REQUIRED BY CHAPTER 553 FLORIDA STATUTES. |
| | |
| | RESPONSE: |
| | PLANS SUBMITTED NOW CORRESPOND TO THE CURRENT 2017 CODE |
| | BUT THE MODEL SUBMITTED WAS CHANGED. THE NEW MODEL IS |
| | DESIGNED FOR AREAS LOCATED IN WIND EXPOSURE C. THIS |
| | SHED IS GOING TO BE INSTALLED IN AN AREA WITH WIND |
| | EXPOSURE D. (SEC. R301.2.1.4 FBC-RESIDENTIAL). NEED TO |
| | PROVIDE APPROVED PLANS FOR WIND EXPOSURE D. |
| | NOTE: DRAWINGS FOR MODEL SHED SUBMITTED ON THE THE |
| | FIRST REVIEW WERE DESIGNED FOR WIND EXPOSURE D. THIS |
| | MODEL WAS OK EXCEPT THAT IT NEED IT TOBE UPDATED WITH |
| | THE CURRENT 2017 CODE. |
| | |
| | |
| | 2- SITE SPECIFIC ENGINEERING SUBMITTED FOR THE |
| | ATTACHMENT OF THE SHED: |
| | |
| | A) OK. |
| | |
| | ORIGINAL COMMENT: |
| | B) SITE SPECIFIC ENGINEERING NEEDS TO HAVE THE ORIGINAL |
| | SEAL AND SIGNATURE OF THE ENGINEER AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES WHEN SUBMITTING |
| | DOCUMENTS/PLANS FOR PUBLIC RECORDS. PROVIDE BOTH COPIES |
| | WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NEED ORIGINAL SEAL AND SIGNATURE OF THE |
| | ENGINEER. THIS SITE SPECIFIC ENGINEERING IS NOT PART OF |
| | THE MANUFACTURED BUILDING APPROVED PLANS. THAT IS WHY |
| | SITE SPECIFIC ENGINEERING WITH ENGINEER'S ORIGINAL SEAL |
| | AND SIGNATURE IS REQUIRED. |
| | |
| | ORIGINAL COMMENT: |
| | C) CLEARLY MARK WHICH TIE-DOWN DETAIL IS GOING TO BE |
| | USED. SEC. 107.2.1 CITY AMENDMENTS. |
| | NOTE: BUILDING IS LOCATED IN EXPOSURE D. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. THIS NEEDS TO BE DONE BY THE ENGINEER |
| | RESPONSIBLE FOR THE SITE SPECIFIC ENGINEERING. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |