Plan Review Notes
Plan Review Notes For Permit 19101016
Permit Number 19101016
Review Stop B
Sequence Number 2
Notes
Date Text
2020-02-05 08:16:03RESIDENTIAL (R3) SHED SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- MANUFACTURED BUILDING PANS SUBMITTED ARE FOR THE
 2014 BUILDING CODE. NEED TO PROVIDE PLANS FOR APPROVED
 MANUFACTURED BUILDING UNDER THE CURRENT 2017 BUILDING
 CODE AS REQUIRED BY CHAPTER 553 FLORIDA STATUTES.
  
 RESPONSE:
 PLANS SUBMITTED NOW CORRESPOND TO THE CURRENT 2017 CODE
 BUT THE MODEL SUBMITTED WAS CHANGED. THE NEW MODEL IS
 DESIGNED FOR AREAS LOCATED IN WIND EXPOSURE C. THIS
 SHED IS GOING TO BE INSTALLED IN AN AREA WITH WIND
 EXPOSURE D. (SEC. R301.2.1.4 FBC-RESIDENTIAL). NEED TO
 PROVIDE APPROVED PLANS FOR WIND EXPOSURE D.
 NOTE: DRAWINGS FOR MODEL SHED SUBMITTED ON THE THE
 FIRST REVIEW WERE DESIGNED FOR WIND EXPOSURE D. THIS
 MODEL WAS OK EXCEPT THAT IT NEED IT TOBE UPDATED WITH
 THE CURRENT 2017 CODE.
  
  
 2- SITE SPECIFIC ENGINEERING SUBMITTED FOR THE
 ATTACHMENT OF THE SHED:
  
 A) OK.
  
 ORIGINAL COMMENT:
 B) SITE SPECIFIC ENGINEERING NEEDS TO HAVE THE ORIGINAL
 SEAL AND SIGNATURE OF THE ENGINEER AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS/PLANS FOR PUBLIC RECORDS. PROVIDE BOTH COPIES
 WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE.
  
 RESPONSE:
 REPEAT COMMENT. NEED ORIGINAL SEAL AND SIGNATURE OF THE
 ENGINEER. THIS SITE SPECIFIC ENGINEERING IS NOT PART OF
 THE MANUFACTURED BUILDING APPROVED PLANS. THAT IS WHY
 SITE SPECIFIC ENGINEERING WITH ENGINEER'S ORIGINAL SEAL
 AND SIGNATURE IS REQUIRED.
  
 ORIGINAL COMMENT:
 C) CLEARLY MARK WHICH TIE-DOWN DETAIL IS GOING TO BE
 USED. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: BUILDING IS LOCATED IN EXPOSURE D.
  
 RESPONSE:
 REPEAT COMMENT. THIS NEEDS TO BE DONE BY THE ENGINEER
 RESPONSIBLE FOR THE SITE SPECIFIC ENGINEERING.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  