Plan Review Notes
Plan Review Notes For Permit 19101003
Permit Number 19101003
Review Stop P
Sequence Number 3
Notes
Date Text
2021-07-19 11:54:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 7/19/2021 19101003
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. THIRD REQUEST; PER WPB FBC 107.2.1, INFORMATION ON
 PLAN SHEET P-1; WATER HEATER SCHEDULE PLAN STATES
 EXISTING WATER HEATER DETAIL SHALL COMPLY WITH FBC RES
 P2801 AND P2903.4 (THERMAL EXPANSION CONTROL
 2. PER WPB FBC 107.2.1, PROVIDE NOTE REQUIRING WATER
 HAMMER ARRESTORS FOR DISHWASHER AND ICE LINE AND
 WASHING MACHINE IN ACCORDANCE WITH FBC RES P2903.5.
 3.. PER FBC PL 2017 406.2WASTE CONNECTION.
 THE WASTE FROM AN AUTOMATIC CLOTHES WASHER SHALL
 DISCHARGE THROUGH AN AIR BREAK INTO A STANDPIPE IN
 ACCORDANCE WITH SECTION 802.3.3 OR INTO A LAUNDRY SINK.
 THE TRAP AND FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER STANDPIPE SHALL BE NOT LESS THAN 2 INCHES (51
 MM) IN DIAMETER. THE FIXTURE DRAIN FOR THE STANDPIPE
 SERVING AN AUTOMATIC CLOTHES WASHER SHALL CONNECT TO A
 3-INCH (76 MM) OR LARGER DIAMETER FIXTURE BRANCH OR
 STACK. AUTOMATIC CLOTHES WASHERS THAT DISCHARGE BY
 GRAVITY SHALL BE PERMITTED TO DRAIN TO A WASTE RECEPTOR
 OR AN APPROVED TRENCH DRAIN.
 4. RE: A-1; FIXTURE SCHEDULE, FLOOR MOUNTED TUB FILLER.
 A. PER FBC RES P2713.3, PROVIDE A TEMPERATURE LIMITING
 DEVICE CONFORMING TO ASSE 1070 OR SHOW THAT THE TUB
 FILL VALVE CONFORMS TO ONE OF THE FOLLOWING; ASSE 1016,
 ASMEA112.1016 OR CSA B125.16 AS REQUIRED BY FBC RES
 P2708.4 FOR COMBINATION TUB/SHOWER CONTROL VALVES.
 B. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR CONNECTION
 OF HOT AND COLD WATER SUPPLY LINES TO THE FLOOR MOUNTED
 TUB FILLER; PROVIDE ACCESS TO THE CONNECTIONS IN THE
 CONCRETE SLAB AS REQUIRED BY FBC RES P2906.7.
 5. PER WPB FBC 107.2.1, PROVIDE SIZED SANITARY PLAN
 VIEW AND RISER DIAGRAM FOR THE ADDED SOAKING OR
 WHIRLPOOL TUB IN THE MASTER BATH. PROVIDE TRAP, VENT
 AND POINT OF CONNECTION OF FIXTURE DRAIN COMPLYING WITH
 FBC RES CHAPTERS 30,31 AND 32.
 6. PLAN SHEET P-1 THE SANITARY ISOMETRIC SHALL BE
 REVISED TO COMPLY WITH FBC PL 2017 910.- FBC PL 2017
 915
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  
  