| 2021-07-19 11:54:21 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | 7/19/2021 19101003 |
| | |
| | 3RD REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. THIRD REQUEST; PER WPB FBC 107.2.1, INFORMATION ON |
| | PLAN SHEET P-1; WATER HEATER SCHEDULE PLAN STATES |
| | EXISTING WATER HEATER DETAIL SHALL COMPLY WITH FBC RES |
| | P2801 AND P2903.4 (THERMAL EXPANSION CONTROL |
| | 2. PER WPB FBC 107.2.1, PROVIDE NOTE REQUIRING WATER |
| | HAMMER ARRESTORS FOR DISHWASHER AND ICE LINE AND |
| | WASHING MACHINE IN ACCORDANCE WITH FBC RES P2903.5. |
| | 3.. PER FBC PL 2017 406.2WASTE CONNECTION. |
| | THE WASTE FROM AN AUTOMATIC CLOTHES WASHER SHALL |
| | DISCHARGE THROUGH AN AIR BREAK INTO A STANDPIPE IN |
| | ACCORDANCE WITH SECTION 802.3.3 OR INTO A LAUNDRY SINK. |
| | THE TRAP AND FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER STANDPIPE SHALL BE NOT LESS THAN 2 INCHES (51 |
| | MM) IN DIAMETER. THE FIXTURE DRAIN FOR THE STANDPIPE |
| | SERVING AN AUTOMATIC CLOTHES WASHER SHALL CONNECT TO A |
| | 3-INCH (76 MM) OR LARGER DIAMETER FIXTURE BRANCH OR |
| | STACK. AUTOMATIC CLOTHES WASHERS THAT DISCHARGE BY |
| | GRAVITY SHALL BE PERMITTED TO DRAIN TO A WASTE RECEPTOR |
| | OR AN APPROVED TRENCH DRAIN. |
| | 4. RE: A-1; FIXTURE SCHEDULE, FLOOR MOUNTED TUB FILLER. |
| | A. PER FBC RES P2713.3, PROVIDE A TEMPERATURE LIMITING |
| | DEVICE CONFORMING TO ASSE 1070 OR SHOW THAT THE TUB |
| | FILL VALVE CONFORMS TO ONE OF THE FOLLOWING; ASSE 1016, |
| | ASMEA112.1016 OR CSA B125.16 AS REQUIRED BY FBC RES |
| | P2708.4 FOR COMBINATION TUB/SHOWER CONTROL VALVES. |
| | B. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR CONNECTION |
| | OF HOT AND COLD WATER SUPPLY LINES TO THE FLOOR MOUNTED |
| | TUB FILLER; PROVIDE ACCESS TO THE CONNECTIONS IN THE |
| | CONCRETE SLAB AS REQUIRED BY FBC RES P2906.7. |
| | 5. PER WPB FBC 107.2.1, PROVIDE SIZED SANITARY PLAN |
| | VIEW AND RISER DIAGRAM FOR THE ADDED SOAKING OR |
| | WHIRLPOOL TUB IN THE MASTER BATH. PROVIDE TRAP, VENT |
| | AND POINT OF CONNECTION OF FIXTURE DRAIN COMPLYING WITH |
| | FBC RES CHAPTERS 30,31 AND 32. |
| | 6. PLAN SHEET P-1 THE SANITARY ISOMETRIC SHALL BE |
| | REVISED TO COMPLY WITH FBC PL 2017 910.- FBC PL 2017 |
| | 915 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |