Plan Review Notes
Plan Review Notes For Permit 19101003
Permit Number 19101003
Review Stop P
Sequence Number 2
Notes
Date Text
2020-03-10 11:49:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE
 SIZE(CAPACITY) OF EXISTING WATER HEATER. PLEASE NOTE
 THAT THREE FIXTURES, A LARGE SOAKING OR WHIRLPOOL TUB,
 A SHOWER AND A LAVATORY, ALL REQUIRING HOT WATER HAVE
 BEEN ADDED TO THE PROJECT. THE INFORMATION ON PLAN
 SHEET P-1; WATER HEATER SCHEDULE PLAN STATES EXISTING
 WATER HEATER BUT PROVIDES NO DETAILS. PROVIDE AS A
 MINIMUM THAT THE EXISTING CAPACITY WILL ADEQUATELY
 SUPPORT ALL PLUMBING FIXTURES IN THE HOUSE, INCLUSIVE
 OF LAUNDRY FACILITIES. PROVIDE CALCULATIONS; REFER TO
 FBC RES P2903.6 AND TABLES P2903.6/P2903.6(1). IF
 EXISTING WATER HEATER IS NOT ADEQUATE, PROVIDE A NEW
 WATER HEATER AND SPECIFICATION/SCHEDULE. DETAIL SHALL
 COMPLY WITH FBC RES P2801 AND P2903.4 (THERMAL
 EXPANSION CONTROL). ADDITIONALLY, SHOW LOCATION ON THE
 FLOOR PLAN.
 2. A FULL BATHROOM GROUP AS WELL AS AN ADDITIONAL
 SHOWER HAS EACH BEEN ADDED TO THE PROJECT. PROVIDE AS
 MINIMUM THAT THE EXISTING WATER SERVICE WILL ADEQUATELY
 SUPPORT ALL PLUMBING FIXTURES IN THE HOUSE. PROVIDE
 CALCULATIONS; REFER TO FBC RES P2903.6 AND TABLES
 P2903.6/P2903.6(1). IF EXISTING SERVICE IS NOT
 ADEQUATE, THEN UPGRADE WATER SERVICE AND DISTRIBUTION
 TO ADEQUATELY SUPPORT ALL PLUMBING FIXTURES, INCLUDING
 THE LAUNDRY FACILITIES.
 3. PER WPB FBC 107.2.1, PROVIDE NOTE REQUIRING WATER
 HAMMER ARRESTORS FOR DISHWASHER AND ICE LINE AND
 WASHING MACHINE IN ACCORDANCE WITH FBC RES P2903.5.
 4. PER WPB FBC 107.2.1, SHOW LOCATION OF THE EXISTING
 CLOTHES WASHER AND IF APPLICABLE, THE LAUNDRY TUB.
 5. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLAN REQUIRING
 NEW SHOWER/ TUB VALVES SHALL COMPLY WITH FBC RES
 P2708.4 AND P2708.5.
  
 6. RE: A-1; FIXTURE SCHEDULE, FLOOR MOUNTED TUB FILLER.
 A. PER FBC RES P2713.3, PROVIDE A TEMPERATURE LIMITING
 DEVICE CONFORMING TO ASSE 1070 OR SHOW THAT THE TUB
 FILL VALVE CONFORMS TO ONE OF THE FOLLOWING; ASSE 1016,
 ASMEA112.1016 OR CSA B125.16 AS REQUIRED BY FBC RES
 P2708.4 FOR COMBINATION TUB/SHOWER CONTROL VALVES.
 B. PROVIDE BACKFLOW PREVENTION DEVICE FOR THE HAND-HELD
 SHOWER; COMPLY WITH FBC RES P2708.5
 C. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR CONNECTION
 OF HOT AND COLD WATER SUPPLY LINES TO THE FLOOR MOUNTED
 TUB FILLER; PROVIDE ACCESS TO THE CONNECTIONS IN THE
 CONCRETE SLAB AS REQUIRED BY FBC RES P2906.7.
  
 7. PER WPB FBC 107.2.1, PROVIDE SIZED SANITARY PLAN
 VIEW AND RISER DIAGRAM FOR THE ADDED SOAKING OR
 WHIRLPOOL TUB IN THE MASTER BATH. PROVIDE TRAP, VENT
 AND POINT OF CONNECTION OF FIXTURE DRAIN COMPLYING WITH
 FBC RES CHAPTERS 30,31 AND 32.
 8. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
 9. PLAN SHEET P-1 ON ONE OF THE TWO RESUBMITTALS IS
 MISSING THE ENGINEER?S STAMP/SEAL. PLEASE WHEN
 RESUBMITTING BE SURE THAT ALL PLANS ARE SIGNED AND
 STAMPED/SEALED AS REQUIRED BY FLORIDA ADMINISTRATIVE
 CODE AND FLORIDA STATUTES
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19101003 212 GREGORY PL
  