Plan Review Notes
Plan Review Notes For Permit 19101003
Permit Number 19101003
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2021-07-27 16:26:22SIGNATURE REVIEW COMMENTS.
  
 1- NONE OF THE PLANS SUBMITTED HAVE THE ENGINEER'S OF
 RECORD SEAL AND SIGNATURE. ALL PLANS NEED TO HAVE THE
 ENGINEER'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY 471
 F.S. WHEN SUBMITTING PLANS /DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NOTE:
 PLANS CAN BE UPLOADED TO PROJECTDOX WITH DIGITAL
 SIGNATURE OR HARD COPIES WITH ENGINEER'S ORIGINAL
 SIGNATURE/SEAL MAY BE DROPPED OFF IN CITY HALL.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]