| 2019-11-05 19:04:31 | RESIDENTIAL (R3) EXTERIOR DECK BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1- THE FRAMING OF THE PROPOSED WOOD DECK DOESN'T SEEM |
| | TO BE A CONVENTIONAL FLOOR FRAMING DESIGN. ENGINEER OF |
| | RECORD TO PROVIDE A COMPLETE ENGINEERING ANALYSIS |
| | SHOWING HOW THE PROPOSED FRAMING WILL MEET ALL DESIGN |
| | LOADS. LIVE LOADS, DEAD LOADS, WIND LOADS, ETC. ALSO, |
| | ENGINEER TO SPECIFY THE THICKNESS OF THE DECK BOARD AND |
| | PROVIDE COMPLETE SPECIFICATIONS FROM DECK MANUFACTURER |
| | SHOWING THAT THE DECK BOARD MEETS THE DESIGN SPAN SHOWN |
| | ON PLANS. SEC. 107.2.1.2 CITY AMENDMENTS AND SEC. R507 |
| | FBC-RESIDENTIAL. |
| | |
| | 2- ENGINEER TO SPECIFY ALL DESIGN LOADS INCLUDING THE |
| | LIVE LOADS AS REQUIRED BY SEC. R301.1 AND TABLE R301.5 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- THERE IS A DISCREPANCY BETWEEN THE ENGINEER PLANS |
| | SUBMITTED AND THE "ITEM AND DESCRIPTION" SPECIFIED ON |
| | THE CONTRACTOR'S COPY OF CONTRACT SUBMITTED. REVISE AS |
| | REQUIRED TO MATCH TO AVOID CONFLICTS/DELAYS. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- BASED ON PLANS SUBMITTED, IT LOOKS LIKE THE 4X4 WOOD |
| | POSTS ARE GOING TO BE BURIED IN THE GROUND. PROVIDE |
| | SPECIFICATIONS FOR THE TYPE OF WOOD THAT IS DESIGNED |
| | FOR THIS TYPE OF INSTALLATION. NOTE: COORDINATE WITH |
| | SPECIFICATIONS SHOWN ON THE CONTRACTOR'S CONTRACT. TO |
| | AVOID CONFLICTS/DELAYS. SEC. R317.1.2 FBC-RESIDENTIAL. |
| | |
| | 5- DESIGN CRITERIA ON PLANS SPECIFY THAT THIS IS A |
| | "BUILDING CODE LEVEL II ALTERATION". THIS IS INCORRECT. |
| | THIS IS AN ADDITION (SEC. 507 FBC-EXISTIN BUILDING) . |
| | SEE THE DESCRIPTION OF LEVEL II ALTERATION ON SEC. 504 |
| | FBC-EXISTING BUILDING AND REVISE AS REQUIRED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER FROM THE ENGINEER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |