| Plan Review Notes For Permit 19100947 |
| Permit Number |
19100947 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-21 11:41:17 | CLARIFICATION IS NEEDED PER THE "GENERAL NOTES" LEGEND | | | AS TO WHICH UPRIGHT HEADS WILL REMAIN, AND WHICH | | | UPRIGHT HEADS WILL BE CAPPED OFF. (THERE ARE TWO | | | SYMBOLS FOR EXISTING UPRIGHT HEADS TO REMAIN). | | | ADDITIONALLY, WHAT DOES THE ADDITION OF THE CONCEALED | | | HEADS DO TO THE HYDROCALCULATIONS WHEN INTRODUCED TO | | | THE "EXISTING" UPRIGHTS? | | | | | | S. THOMAS | | | 561-804-4728 |
|