2019-11-04 14:17:532017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19100898
 ADD: 2330 VILLAGE BLVD.
 CONT: BUILT-MOORE LLC
 TEL: 615-925-2075
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 04TH/ 2019
 ACTION: DENIED
  
 1) THE COVERSHEET TS LIST:
 1A) THE 2014 FBC 5TH EDITION AS THE CODE IN AFFECT.
 PLEASE NOTE STATEWIDE THE 6TH EDITION OF THE FBC
 (FAMILY OF CODES INCLUDING ACCESSIBILITY CODE), 2017
 WAS ADOPTED STATEWIDE ON DEC. 31, 2017. PLEASE UPDATE
 YOUR PLANS.
  
 1B) THE 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE CHAPTER 1 ADMINISTRATIVE CODE WAS ADOPTED
 ALSO ON DEC. 31, 2017. PLEASE UPDATE YOUR PLANS.
  
 1C) PLEASE CORRECT THE UNIFIED LAND DEVELOPMENT CODE
 (ULDC) AND REFERENCES TO PALM BEACH COUNTY. THE CITY OF
 WEST PALM BEACH IS UNDER HOME RULE NOT PART OF THE PALM
 BEACH COUNTY JURISDICTION, NOT ANY PART DESIGNATED AS
 MUNICIPAL AREA. PLEASE CORRECT THE PLANS.
  
 1D) PLEASE ALSO NOTE ADDITIONAL REFERENCED DOCUMENTS
 (CHAPTER 35 FGI) FOR CONSTRUCTION AND DESIGN THAT NEED
 TO SHOW COMPLIANCE:
 AGENCY FOR HEALTH CARE ADMINISTRATION (AHCA) FOR
 NURSING HOMES. FGI THE FACILITIES GUIDELINE INSTITUTE/
 (GHCF-14)
  
 1E) FLORIDA ADMINISTRATIVE CODE CHAPTER 59A-4
  
 1F) CHAPTER 400 PART II FLORIDA STATUTES
  
 1G) THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF
 RESIDENTIAL HEALTH CARE, AND SUPPORT FACILITIES. THE
 FACILITIES GUIDELINE INSTITUTE/ GHCF-14 CHAPTER 3.2
 SPECIFIC REQUIREMENTS FOR NURSING HOMES.
  
 1H) 2017 FBC-B SECTION 450.1.3. FLORIDA BUILDING CODE,
 EXISTING BUILDINGS, SECTION 101.2, SCOPE EXEMPTS STATE
 LICENSED FACILITIES SUCH AS NURSING HOMES FROM
 COMPLIANCE WITH THAT CODE. ANY, REPAIRS, ALTERATIONS,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF AN
 EXISTING STATE LICENSED NURSING HOME SHALL COMPLY WITH
 THE APPLICABLE REQUIREMENTS OF THIS CODE AND THIS
 SECTION.
  
 THE LIFE SAFETY SHEET LIST UNDER THE PROJECT SCOPE A
 LEVEL 1 ALTERATION. PLEASE UPDATE THE PLANS. ALL WORK
 IS TO BE CONSIDERED AS NEW WORK AND MEET ALL OF THE
 REQUIREMENTS UNDER ALL OF THE ABOVE CODES AND
 STANDARDS.
  
 2) SHEET R101 THE LIFE SAFETY SHEET:
 2A) HEADING, EXISTING BUILDING DATA MAKES REFERENCE TO
 THE IBC. PLEASE NOTE THE IBC MAYBE THE BASE CODE, BUT
 FLORIDA HAS ADOPTED THE 2017 FAMILY OF FBC CODES. THE
 FLORIDA CODE IS MORE RESTRICTIVE, PLEASE USE THE 2017
 FBC AS YOUR DESIGN CRITERIA AS WELL AS THE REFERENCED
 STANDARDS, FLORIDA STATUTES AND ADMINISTRATIVE CODE FOR
 DESIGN PURPOSES.
  
 2B) THE EXISTING BUILDING DATA HAS LEFT BLANK THE
 CONSTRUCTION TYPE? PLEASE REVIEW THE 2017 FBC-B TABLES
 504.3, 504.4 & 506.2.
  
 2C) PLEASE UPDATE PLANS AS TO THE REFERENCED CODE, NOT
 THE IBC, BUT THE 2017 FBC-B IN REGARDS TO THE OCCUPANCY
 TYPE.
  
 2D) SHEET R-101 THE LIFE SAFETY PLAN: EXISTING BUILDING
 DATA GIVES THE SQUARE FOOT AREA OF 21,041 SQUARE FEET.
 THE P. B. COUNTY GEO NAV MAPPING SHOWS 54,850 SQUARE
 FEET IN AREA. WHY SUCH A DIFFERENCE IN SQ. FOOTAGE?
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 407.5 FOR SMOKE COMPARTMENTS. SMOKE BARRIERS SHALL BE
 PROVIDED TO SUBDIVIDE EVERY STORY USED BY PERSONS
 RECEIVING CARE, TREATMENT OR SLEEPING AND TO DIVIDE
 OTHER STORIES WITH AN OCCUPANT LOAD OF 50 OR MORE
 PERSONS, INTO NO FEWER THAN TWO SMOKE COMPARTMENTS.
 SUCH STORIES SHALL BE DIVIDED INTO SMOKE COMPARTMENTS
 WITH AN AREA OF NOT MORE THAN 22,500 SQUARE FEET (2092
 M2) IN GROUP I-2, CONDITION 1, AND NOT MORE THAN 40,000
 SQUARE FEET (3716 M2) IN GROUP I-2, CONDITION 2, AND
 THE DISTANCE OF TRAVEL FROM ANY POINT IN A SMOKE
 COMPARTMENT TO A SMOKE BARRIER DOOR SHALL BE NOT
 GREATER THAN 200 FEET (60 960 MM). THE SMOKE BARRIER
 SHALL BE IN ACCORDANCE WITH SECTION 709SECTION 709.
  
 2E) THE LIFE SAFETY PLAN SHOWS A WALL LEGEND FOR THE
 FIRE AND SMOKE RATINGS OF WALLS. PLEASE NOTE THERE ARE
 NO RATING OF WALLS ON THE PLANS. THE PLANS CURRENTLY
 UNDER THIS REVIEW DO NOT SHOW COMPLIANCE WITH SECTION
 407.5 NOR INFORMATION ON THE DOORS LEADING FROM EACH
 SMOKE COMPARTMENT.
  
 3) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE
 THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW
 PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  