| 2019-11-05 09:25:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET M 1.01 - FLAG NOTE # 3 STATES A 10X16 ACCESS |
| | CLEAN OUT DOOR. |
| | |
| | PER NFPA 96 |
| | |
| | 7.1.4.2 ALL HORIZONTAL DUCTS SHALL BE PROVIDED WITH |
| | ACCESS IN |
| | ACCORDANCE WITH 7.4.1. |
| | |
| | 7.4.1 HORIZONTAL DUCTS. |
| | |
| | 7.4.1.1 ON HORIZONTAL DUCTS, AT LEAST ONE 508 MM ? 508 |
| | MM |
| | (20 IN. ? 20 IN.) OPENING SHALL BE PROVIDED FOR |
| | PERSONNEL ENTRY. |
| | |
| | 7.4.1.2 WHERE AN OPENING OF THE SIZE SPECIFIED IN |
| | 7.4.1.1 IS |
| | NOT POSSIBLE, OPENINGS LARGE ENOUGH TO PERMIT THOROUGH |
| | CLEANING SHALL BE PROVIDED AT 3.7 M (12 FT) INTERVALS. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS IN |
| | COMPLIANCE. |
| | |
| | |
| | 2) SHEET M 1.01 - A SLOPE PERCENT IS NOT PROVIDED OR |
| | READILY INDICATED |
| | |
| | PER NFPA 96 |
| | |
| | 7.1.4 ALL DUCTS SHALL BE INSTALLED WITH A MINIMUM 2 |
| | PERCENT |
| | SLOPE ON HORIZONTAL RUNS UP TO 22.86M(75 FT) AND A |
| | MINIMUM |
| | 8 PERCENT SLOPE ON HORIZONTAL RUNS GREATER THAN 22.86 M |
| | (75 FT). |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | |
| | 3) SHEET M 1.01- THERE ARE NO INDICATIONS OF REQUIRED |
| | SIGNAGE. |
| | |
| | PER NFPA 96 |
| | |
| | 7.1.6 A SIGN STATING THE FOLLOWING SHALL BE PLACED ON |
| | ALL ACCESS |
| | PANELS: |
| | ACCESS PANEL? DO NOT OBSTRUCT |
| | |
| | |
| | |
| | 4) SHEET 1.11 - THERE ARE NO INDICATIONS OF DIMENSIONS |
| | ON THE ROOF TOP |
| | |
| | PER NFPA 96 |
| | |
| | 7.8.2 ROOFTOP TERMINATIONS. |
| | 7.8.2.1 ROOFTOP TERMINATIONS SHALL BE ARRANGED WITH OR |
| | PROVIDED |
| | WITH THE FOLLOWING: |
| | (1) A MINIMUM OF 3 M (10 FT) OF HORIZONTAL CLEARANCE |
| | FROM |
| | THE OUTLET TO ADJACENT BUILDINGS, PROPERTY LINES, AND |
| | AIR |
| | INTAKES |
| | (2) A MINIMUM OF 1.5 M (5 FT) OF HORIZONTAL CLEARANCE |
| | FROM |
| | THE OUTLET (FAN HOUSING) TO ANY COMBUSTIBLE STRUCTURE |
| | (3) A VERTICAL SEPARATION OF 0.92 M (3 FT) BELOW ANY |
| | EXHAUST |
| | OUTLETS FOR AIR INTAKES WITHIN 3 M (10 FT) OF THE |
| | EXHAUST |
| | OUTLET |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |