| 2019-10-18 14:47:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLANS HAVE TOO MANY DISCREPANCIES FOR A THOROUGH |
| | REVIEW. RISER DIAGRAM AND FLOOR PLAN SHOWS 4 PANELS IN |
| | THE TWO UNITS. HOWEVER, THERE ARE ONLY 2 PANEL |
| | SCHEDULES FOR THE TWO 100 AMP PANELS. WHAT LOAD IS |
| | BEING FED FROM THE 150 AMP PANELS? IT APPEARS THAT THE |
| | DESIGNER CHANGED THE DESCRIPTION OF THE TWO150 AMP |
| | PANELS AND INITIALED THEM, BUT THERE ARE NO FURTHER |
| | DETAILS ABOUT THESE PANELS. PROVIDE CLARIFICATION. ARE |
| | THERE 2 SERVICES ON THIS BUILDING? IF SO, WHERE ARE |
| | THESE SERVICES LOCATED? MAINS ARE REQUIRED TO BE |
| | GROUPED. PROVIDE LOCATION OF ELECTRICAL SERVICE. |
| | PROVIDE DETAIL OF GROUNDING ELECTRODE SYSTEM AND METHOD |
| | OF CONNECTING THE TWO SERVICES. PROVIDE CORRECTIONS AND |
| | CLARIFICATIONS TO CONFIRM CODE COMPLIANCE. WPB FBC |
| | 107.2.1 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION. THE LOAD |
| | CALCULATION ON PLAN IS NOT CODE COMPLIANT. THERE SHOULD |
| | BE A LOAD CALCULATION PROVIDED FOR THE ENTIRE SERVICE, |
| | AS WELL AS FOR EACH PANEL. NEC 215.2, 220, 408.30; FBC |
| | RE E3602.2 |
| | 3. SMOKE ALARMS ARE SHOWN WITHIN 3 FEET OF BATHROOM, |
| | AND IN CLOSE PROXIMITY TO COOKING APPLIANCES. PROVIDE |
| | CORRECTION PER FBC RE R314.3. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |