Plan Review Notes
Plan Review Notes For Permit 19100889
Permit Number 19100889
Review Stop P
Sequence Number 4
Notes
Date Text
2020-03-21 13:30:1219100889 2239 PALM BEACH LAKES BLVD
  
 PLUMBING APPROVED W/PROVISO
  
 I. OIL/WATER SEPARATOR DRAW OFF TANK
 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, REGARDING
 THE OIL/WATER SEPARATOR DRAW OFF TANK, PROVIDE AS A
 DEFERRED SUBMITTAL THE FOLLOWING:
 CLARIFICATION AS TO WHETHER THE SYSTEM IS NEW OR
 EXISTING. IF EXISTING, SHOW LOCATION AND PROVIDE
 CERTIFICATION SHOWING COMPLIANCE WITH FLORIDA DEP. IF
 NEW, SUBMIT SPECIFICATION, DETAIL AND LOCATION OF NEW
 TANK AND PIPING. DOCUMENT SHALL BE SUBMITTED, APPROVED
 AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR
 OWN RISK.
 II. DRINKING FOUNTAIN
 1. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH FBC ACC 305 POSITIONED FOR A FORWARD
 APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH FBC ACC 306 SHALL BE PROVIDED
 PER FBC ACC 602.2.
 2. OPERABLE PARTS SHALL COMPLY WITH FBC ACC 309 PER FBC
 ACC 602.3.
 3. SPOUT OUTLETS SHALL BE 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 602.4.
 4.THE SPOUT SHALL BE LOCATED 15 INCHES MINIMUM FROM THE
 VERTICAL SUPPORT AND 5 INCHES MAXIMUM FROM THE FRONT
 EDGE OF THE UNIT, INCLUDING BUMPERS PER FBC ACC 602.5.
 III. BREAKROOM SINK
 1. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH