2020-03-20 16:44:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 19100889 2239 PALM BEACH LAKES BLVD
  
 3RD REVIEW
 PLUMBING COMMENTS:DENIED
 1. CONCERNING ITEM 10 REVIEW 2; SUBMIT MSDS SHEETS FOR
 THE CHEMICALS TO BE USED IN
 THE CHEMICAL DISPENSER AND THE AMOUNTS TO BE STORED AND
 HOW THEY ARE STORED.WPB AMEND. TO FBC SEC. 107.2.1.
 NEW COMMENT: IF ARCHITECT IS TO RESPOND TO THIS THEN HE
 NEEDS TO DO SO PRIOR TO APPROVAL FOR PLUMBING PERMIT.
 2.CONCERNING ITEM 10 REVIEW 2; SUBMIT MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE WATER SOFTENING SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 NEW COMMENT: IF THERE IS NO WATER SOFTENER THEN REMOVE
 REFERENCE TO SOFTENED WATER FOR ITEM W-3 CHEMICAL
 DISPENSING CENTER ON PLAN SHEET P1.1
 3. IS THE OIL/SEPERATOR DRAW OFF TANK AND DRAIN
 EXISTING? IF SO SHOW LOCATION AND PROVIDE CERTIFICATION
 SHOWING COMPLIANCE WITH FLORIDA DEP OR SUBMIT SPEC AND
 DETAIL AND LOCATION OF NEW PIPING AND TANK. CONTACT TIM
 LARGE AT 561-805-6692 FOR FURTHER CLARIFICATION.
  
 PROVISO
 I. DRINKING FOUNTAIN
 1.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH FBC ACC 305 POSITIONED FOR A FORWARD
 APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH FBC ACC 306 SHALL BE PROVIDED
 PER FBC ACC 602.2.
 2.OPERABLE PARTS SHALL COMPLY WITH FBC ACC 309 PER FBC
 ACC 602.3.
 3.SPOUT OUTLETS SHALL BE 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 602.4.
 4.THE SPOUT SHALL BE LOCATED 15 INCHES MINIMUM FROM THE
 VERTICAL SUPPORT AND 5 INCHES MAXIMUM FROM THE FRONT
 EDGE OF THE UNIT, INCLUDING BUMPERS PER FBC ACC 602.5.
 II. BREAKROOM SINK
 1. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
  
  