Plan Review Notes
Plan Review Notes For Permit 19100889
Permit Number 19100889
Review Stop P
Sequence Number 2
Notes
Date Text
2020-01-17 12:58:131) THE PLANS INDICATE AN AIR COMPRESSOR. SUBMIT A
 COMPRESSED AIR RISER DIAGRAM IF ANY RIDGID AIR PIPING
 IS TO BE INSTALLED. SHOW THE TYPE OF MATERIAL, PIPE
 SIZIES, LOCATION OF VALVES, ETC. NOTE: PVC PIPING IS
 NOT PERMITTED TO BE USED FOR COMPRESSED AIR PER
 MANUFACTURER'S SPECIFICATIONS. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE CHEMICAL DISPENSING UNIT.
 IF THIS IS CONNECTED TO THE POTABLE WATER SYSTEM IN ANY
 MANNER A BACKFLOW DEVICE WILL BE REQUIRED. WPB AMEND.
 TO FBC SEC. 107.2.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OIL
 INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. P0.2 - DETAIL #6 - THE OIL INTERCEPTOR SHALL
 COMPLY WITH 2017 FBC - PLUMBING SEC.1003.4.2.1.
 5) THE DRINKING FOUNTAIN SHALL BE LOCATED WHERE IT IS
 ACCESSIBLE TO THE CUSTOMERS. THERE IS A TIRE CHANGING
 MACHINE RIGHT NEXT TO THE DRINKING FOUNTAIN. THIS
 CREATES A POSSIBLE UNSAFE ENVIRONMENT FOR A
 NON-EMPLOYEE USING THIS FIXTURE. UNSAF AND I FIND IT
 HARD TO BELIEVE THAT THE BUSINESS ALLOWS CUSTOMERS IN
 THE WORK AREA DUE TO LIABILITY. IF THIS IS THE CASE, A
 NOTARIZED LETTER FROM THE OWNER OF THE BUSINESS SHALL
 BE SUBMITTED SPECIFICALLY STAING THEAT CUSTOMERS WILL
 BE PERMITTED IN THE WORK AREA AND THAT THE BUSINESS
 OWNER ACCEPTS ALL LIABILITY.
 6) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 2017 FBC-PLUMBING SEC. 410.3.
 7) THE WASHING MACINE SHALL BE INSTALLED ON A MINIMUM 3
 INCH WASTE STACK. 2017 FBC-PLUMBING SEC.406.2.
 8) SUBMIT DETAILS/MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE WASHER SYSTEM. WILL ANY RIDGID PIPING BE
 INSTALLED FOR THIS SYSTEM? IF SO, SUBMIT A PIPING
 DIAGRAM SHOWING PIPE MATERIAL, PIPE SIZES, VALVES, ETC.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POINT
 OF USE WATER HEATERS AT THE LAVATORIES.WPB AMEND. TO
 FBC SEC. 107.2.1.
 10) SUBMIT MSDS SHEETS FOR THE CHEMICALS TO BE USED IN
 THE CHEMICAL DISPENSER AND THE AMOUNTS TO BE STORED AND
 HOW THEY ARE STORED.WPB AMEND. TO FBC SEC. 107.2.1.
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE WATER SOFTENING SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 12) THE IRRIGATION SYSTEM WILL NEED A SEPARATE BACKFLOW
 PREVENTION DEVICE AND A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE BACKFLOW PER THE CITY OF WEST PALM
 BEACH CROSS CONNECTION CONTROL MANUAL.
 13) A LINT INTERCEPTTOR IS REQUIRED PER 2017
 FBC-PLUMBING SEC1003.6. AFTER DOING ADDITIONAL RESEARCH
 IN THE IPC COMMENTARY, EXCEPTION #2 REFERS TO WASHING
 MACHINES THAT WOULD BE LOCATED IN COMMON LAUNDRY ROOMS
 IN RESIDENTIAL BUILDINGS, NOT IN A COMMECIAL BUILDING,
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  