| 2020-01-17 12:58:13 | 1) THE PLANS INDICATE AN AIR COMPRESSOR. SUBMIT A |
| | COMPRESSED AIR RISER DIAGRAM IF ANY RIDGID AIR PIPING |
| | IS TO BE INSTALLED. SHOW THE TYPE OF MATERIAL, PIPE |
| | SIZIES, LOCATION OF VALVES, ETC. NOTE: PVC PIPING IS |
| | NOT PERMITTED TO BE USED FOR COMPRESSED AIR PER |
| | MANUFACTURER'S SPECIFICATIONS. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION MANUAL FOR THE CHEMICAL DISPENSING UNIT. |
| | IF THIS IS CONNECTED TO THE POTABLE WATER SYSTEM IN ANY |
| | MANNER A BACKFLOW DEVICE WILL BE REQUIRED. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OIL |
| | INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SHT. P0.2 - DETAIL #6 - THE OIL INTERCEPTOR SHALL |
| | COMPLY WITH 2017 FBC - PLUMBING SEC.1003.4.2.1. |
| | 5) THE DRINKING FOUNTAIN SHALL BE LOCATED WHERE IT IS |
| | ACCESSIBLE TO THE CUSTOMERS. THERE IS A TIRE CHANGING |
| | MACHINE RIGHT NEXT TO THE DRINKING FOUNTAIN. THIS |
| | CREATES A POSSIBLE UNSAFE ENVIRONMENT FOR A |
| | NON-EMPLOYEE USING THIS FIXTURE. UNSAF AND I FIND IT |
| | HARD TO BELIEVE THAT THE BUSINESS ALLOWS CUSTOMERS IN |
| | THE WORK AREA DUE TO LIABILITY. IF THIS IS THE CASE, A |
| | NOTARIZED LETTER FROM THE OWNER OF THE BUSINESS SHALL |
| | BE SUBMITTED SPECIFICALLY STAING THEAT CUSTOMERS WILL |
| | BE PERMITTED IN THE WORK AREA AND THAT THE BUSINESS |
| | OWNER ACCEPTS ALL LIABILITY. |
| | 6) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | 2017 FBC-PLUMBING SEC. 410.3. |
| | 7) THE WASHING MACINE SHALL BE INSTALLED ON A MINIMUM 3 |
| | INCH WASTE STACK. 2017 FBC-PLUMBING SEC.406.2. |
| | 8) SUBMIT DETAILS/MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE WASHER SYSTEM. WILL ANY RIDGID PIPING BE |
| | INSTALLED FOR THIS SYSTEM? IF SO, SUBMIT A PIPING |
| | DIAGRAM SHOWING PIPE MATERIAL, PIPE SIZES, VALVES, ETC. |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POINT |
| | OF USE WATER HEATERS AT THE LAVATORIES.WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 10) SUBMIT MSDS SHEETS FOR THE CHEMICALS TO BE USED IN |
| | THE CHEMICAL DISPENSER AND THE AMOUNTS TO BE STORED AND |
| | HOW THEY ARE STORED.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION |
| | MANUAL FOR THE WATER SOFTENING SYSTEM. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 12) THE IRRIGATION SYSTEM WILL NEED A SEPARATE BACKFLOW |
| | PREVENTION DEVICE AND A SEPARATE PERMIT WILL BE |
| | REQUIRED FOR THE BACKFLOW PER THE CITY OF WEST PALM |
| | BEACH CROSS CONNECTION CONTROL MANUAL. |
| | 13) A LINT INTERCEPTTOR IS REQUIRED PER 2017 |
| | FBC-PLUMBING SEC1003.6. AFTER DOING ADDITIONAL RESEARCH |
| | IN THE IPC COMMENTARY, EXCEPTION #2 REFERS TO WASHING |
| | MACHINES THAT WOULD BE LOCATED IN COMMON LAUNDRY ROOMS |
| | IN RESIDENTIAL BUILDINGS, NOT IN A COMMECIAL BUILDING, |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |